| 2001-07-09 00:00:00 | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | ARE THE BUILDING PLANS THE SAME FOR |
| | SUBDIVISION 3A AND 3B. |
| | |
| | PLAN REVIEW COMMENTS FOR BUILDINGS. |
| | 1) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR ENTRY GATES. WHAT PROVISIONS HAVE |
| | BEEN MADE FOR FIRE AND PARAMEDICAL |
| | ACCESS INTO THE COMPLEX. ARE THE |
| | SECURITY GATES EQUIPPED WITH EMERGENCY |
| | POWER SHOULD LOSS OF POWER OCCURS. |
| | MINIMUM ACCESS TO BE AT LEAST 20 FEET |
| | IN CLEAR WIDTH. |
| | 2) PLEASE BE ADVISED THAT CITY CODE |
| | SECTION 11-4 REQUIRES THAT NOT ITEMS |
| | BE PLACED WITHIN 18 FEET OF FIRE |
| | HYDRANTS. ALSO WET FIRE HYDRANTS ARE |
| | REQUIRED PRIOR TO, DURING AND AFTER |
| | CONSTRUCTION. |
| | 3) BUILDING ADDRESSES REQUIRED PER CITY |
| | CODE 3343-00. |
| | 4) PLEASE PROVIDE PRODUCT APPROVALS FOR |
| | 8X8 GLASS BLOCKS FOR THE ONE HOUR FIRE |
| | RATING SHOWN ON PAGE A2.0.1. |
| | 5) COULD NOT LOCATE FIRE HYDRANT |
| | LOCATIONS FOR SUBDIVISION 3B ON WATER |
| | AND SEWER PLANS. |
| | 6) BUILDINGS ARE REQUIRED TO HAVE FIRE |
| | ALARM SYSTEMS IF THEY ARE THREE STORIES |
| | OR MORE OR IF THEY CONTAIN ELEVEN |
| | LIVING UNITS. SEPARATE PLANS AND PERMITS |
| | REQUIRED FOR THESE CLASS A OR FULLY |
| | ADDRESSABLE FIRE ALARM SYSTEMS. |