Plan Review Notes
Plan Review Notes For Permit 01070074
Permit Number 01070074
Review Stop R
Sequence Number 1
Notes
Date Text
2001-07-12 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALCULATIONS.
  
 4) THE WALL SECTION ON SHEET 2 INDICATES
 2X6 STUD WALLS AND 2X4 TOP AND BOTTOM
 PLATES.PLEASE CLARIFY.
  
 5) THE WALL SECTION ON SHEET 2 INDICATES
 FIBERGLASS ROOF SHINGLES,SHEET 1 AND THE
 PRODUCT APPROVAL ARE FOR TILE. PLEASE
 CLARIFY.
  
 6) THE DETAIL FOR TRUSSES A-1 AND A-2 DO
 NOT INDICATE A LEDGER AT THE BOTTOM CORD
 WHERE THE TRUSS HANGER SHOULD BE
 LOCATED. INDICATE THE STRAP OR OTHER
 APPROPRIATE CONNECTOR THAT WILL BE USED
 ON THE TOP CORD.
  
 7) THE PROPER HANGER FOR PLATED TRUSS
 PRODUCTS IS MODEL HUS AND NOT HU AS
 INDICATED ON SHEET 4. PLEASE CORRECT.
  
 8) MSTA 18 STRAPS ARE NOT ENGINEERED FOR
 CONNECTING TRUSSES TO EXTERIOR WALLS,
 THEY DO NOT PROVIDE RESISTANCE TO
 LATERAL FORCES. SPECIFY AN APPROPRIATE
 TRUSS TO WALL CONNECTOR.
  
 9) INDICATE THE CONNECTORS THAT WILL BE
 USED TO ACHIEVE A CONTINOUS LOAD PATH
 FROM THE FOUNDATION TO THE ROOF.
  
 10) THE TOTAL ROOF LL AND DL ON SHEET 5
 IS 47 PSF AND ON SHEET 4 IS 55 PSF.
 PLEASE CORRECT.
  
 11) THE DESIGN CERTIFICATION FORM ON
 SHEET 5 LISTS 1994 SBC. THE CURRENT CODE
 FOR THE CITY OF WPB IS THE 1997 SBC.
 PLEASE CORRECT. SEE UPDATED CITY FORM
 ATTACHED.
  
 12) DETAILS ON SHEET 5 ARE FOR CONCRETE
 BLOCK CONSTRUCTION AND THE OTHER
 DRAWINGS INDICATE WOOD FRAME. PLEASE
 CLARIFY.
  
 13) INDICATE THE ATTACHMENT OF NEW WALLS
 TO EXISTING STRUCTURE.
  
 14) THERE ARE(2) SHEET 1S IN EACH SET OF
 PLANS.
  
 15) PROVIDE STRUCTURAL DETAILS OF
 OPENING TO ADDITION, WHERE EXISTING
 EXTERIOR WALL IS BEING REMOVED AND THE
 UPPER PORTION OF THE WALL APPEARS TO
 REMAIN. PLEASE CLARIFY.
  
 16) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - AWNING WINDOW (NEED ADDITIONAL COPY)
 - ALUMINUM FIXED WINDOW (ONLY ONE PAGE
 OF REPORT WAS SUBMITTED; NEED 2 COMPLETE
 COPIES)
 - STRUCTURAL MULLIONS (FRONT WINDOWS)
 - ROOF TILE (NEED ADDITIONAL COPY)
 - STORM PANELS (NEED ADDITIONAL COPY)
  
 17) PROVIDE POSITIVE AND NEGATIVE
 PRESSURES FOR EXTERIOR WINDOWS,DOORS AND
 OVERHEAD GARAGE DOORS IN NEW ADDITIONS.
  
 18) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS.(2 COPIES)
 INDICATE THE SPECIFIC ANCHOR TYPE AND
 METHOD OF MOUNTING THAT WILL BE USED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202