| 2001-09-15 00:00:00 | DENIED |
| | REFERENCES: SPC-94 - SGC-97 - FHA-98 |
| | DESIGN MANUAL |
| | (1) SHEETS A002 & A302. PLEASE INDICATE |
| | SPECIFICATION A OR B AS REQUIRED IN FHA- |
| | 98 REQUIREMENT 7B BATHROOM REQUIREMENTS. |
| | (2) SHEET A302 DETAIL & FLOOR PLAN, BATH |
| | ROOM 1-009F. PARALLEL APPROACH TO BASIN, |
| | BASIN TO BE CENTERED ON 48". |
| | (3) SHEET A302 TYPICAL DORM UNIT A B C. |
| | SHOW CLEAR FLOOR SPACE FOR DRESSING ROOM |
| | BASIN. |
| | (4) REQ. 2 COMMON USE SPACES PAGE 2.27. |
| | SHEET A302 SHOW CLEAR FLOOR SPACE FOR |
| | LAUNDRY AND PANTRY SINKS. FHA-98 |
| | (5) PAGE P002 ELECTRIC WATER HEATER DE- |
| | TAIL. PAN DRAIN (1") AND P&T (FULL SIZE) |
| | TO RUN SEPARATELY TO A FLOOR SINK WITH A |
| | TRAP PRIMER. SPC-94 SECTIONS 507.8.2, |
| | 507.8.4, 507.8.5 AND 802. |
| | (6) PAGE P002 ELECT. WATER HEATER DETAIL |
| | COLD WATER SHUT OFF VALVE TO BE ACCESS- |
| | ABLE WITH OUT THE USE OF LADDERS ECT. |
| | SPC-94 SECT. 610.3.3 |
| | (7) PAGE P201 NO HOT WATER SHOWN TO KIT- |
| | CHEN SINK IN DIRECTORS APT RM #1-009A. |
| | (8) PAGE P201 ROOM #1-022, ELECT. WATER |
| | HEATER DETAIL, WATER HEATER PAN DRAIN TO |
| | RUN 1" TO FLOOR SINK W/TRAP PRIMER NOT |
| | TO FLOOR DRAIN. |
| | (9) PAGE P401 DIRECTORS APT RM #1-009A, |
| | NO COLD WATER TO W/C'S ON WATER RISER. |
| | (10) PAGE P401 NO COLD WATER SHOWN FOR |
| | CENTER LAV IN WOMENS RESTROOM RISER DIA. |
| | (11) PAGE P401 WATER HAMMER ARRESTOR AT |
| | TOP OF DROP IN MENS RESTROOM NOT LOCATED |
| | PROPERLY. PLEASE SHOW PROPER LOCATION |
| | PER WH-PDI 201. |
| | (12) SHEET A-301 RM #1-009B. SHOW CLEAR |
| | FLOOR SPACE FOR KITCHEN PER FHA-98 |
| | (13) SHEET A-208 PLEASE SHOW SECONDARY |
| | ROOF DRAINS. GIVE CALCULATIONS AND SIZE |
| | PER SPC-94 SECTION 1108.5 & FIG 1109.3. |
| | (14) SHEET C-1, FIRE AND IRRIGATION BACK |
| | FLOW PREVENTERS NOT SHOWN. SEE COMMENT |
| | #5 OF PLAN REVIEW DATED 7-15-01. |
| | (15) PAGES P002, P201, & P401. INFORMAT- |
| | ION STILL REQUIRED FOR GAS PERMIT APPLI- |
| | CATION. #1 TYPE OF MATERIAL, #2 TYPE OF |
| | GAS & #3 MANUFACTURE INFORMATION FOR GAS |
| | BOILER. |
| | (16) PAGE P201 PLEASE PROVIDE A CONDEN- |
| | SATE RISER DIAGRAM WITH PIPE SIZES AND |
| | SHOW LOAD OF EACH NUMBERED RISER. |
| | (17) PAGE P203 PLEASE PROVIDE A RISER |
| | DIAGRAM WITH PIPE SIZE FOR TRENCH DRAINS |
| | FOR THE FOURTH AND FIFTH FLOOR PARKING |
| | GARAGE. |
| | (18) PAGE P401 GAS RISER DIAGRAM. ARE |
| | ALL 4 SHUT OFF VALVES NECESSARY? |
| | (19) PAGE P301 FLOOR DRAINS AT THE WATER |
| | CLOSETS, ARE ALL THESE NECESSARY? |
| | (20) PAGES P203 & P204, KEY NOTES #2. |
| | PLEASE CHANGE TO REFLECT CHANGE ON P205 |
| | SAME NOTE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT. 8377 |