Plan Review Notes
Plan Review Notes For Permit 01070072
Permit Number 01070072
Review Stop P
Sequence Number 2
Notes
Date Text
2001-09-15 00:00:00DENIED
 REFERENCES: SPC-94 - SGC-97 - FHA-98
 DESIGN MANUAL
 (1) SHEETS A002 & A302. PLEASE INDICATE
 SPECIFICATION A OR B AS REQUIRED IN FHA-
 98 REQUIREMENT 7B BATHROOM REQUIREMENTS.
 (2) SHEET A302 DETAIL & FLOOR PLAN, BATH
 ROOM 1-009F. PARALLEL APPROACH TO BASIN,
 BASIN TO BE CENTERED ON 48".
 (3) SHEET A302 TYPICAL DORM UNIT A B C.
 SHOW CLEAR FLOOR SPACE FOR DRESSING ROOM
 BASIN.
 (4) REQ. 2 COMMON USE SPACES PAGE 2.27.
 SHEET A302 SHOW CLEAR FLOOR SPACE FOR
 LAUNDRY AND PANTRY SINKS. FHA-98
 (5) PAGE P002 ELECTRIC WATER HEATER DE-
 TAIL. PAN DRAIN (1") AND P&T (FULL SIZE)
 TO RUN SEPARATELY TO A FLOOR SINK WITH A
 TRAP PRIMER. SPC-94 SECTIONS 507.8.2,
 507.8.4, 507.8.5 AND 802.
 (6) PAGE P002 ELECT. WATER HEATER DETAIL
 COLD WATER SHUT OFF VALVE TO BE ACCESS-
 ABLE WITH OUT THE USE OF LADDERS ECT.
 SPC-94 SECT. 610.3.3
 (7) PAGE P201 NO HOT WATER SHOWN TO KIT-
 CHEN SINK IN DIRECTORS APT RM #1-009A.
 (8) PAGE P201 ROOM #1-022, ELECT. WATER
 HEATER DETAIL, WATER HEATER PAN DRAIN TO
 RUN 1" TO FLOOR SINK W/TRAP PRIMER NOT
 TO FLOOR DRAIN.
 (9) PAGE P401 DIRECTORS APT RM #1-009A,
 NO COLD WATER TO W/C'S ON WATER RISER.
 (10) PAGE P401 NO COLD WATER SHOWN FOR
 CENTER LAV IN WOMENS RESTROOM RISER DIA.
 (11) PAGE P401 WATER HAMMER ARRESTOR AT
 TOP OF DROP IN MENS RESTROOM NOT LOCATED
 PROPERLY. PLEASE SHOW PROPER LOCATION
 PER WH-PDI 201.
 (12) SHEET A-301 RM #1-009B. SHOW CLEAR
 FLOOR SPACE FOR KITCHEN PER FHA-98
 (13) SHEET A-208 PLEASE SHOW SECONDARY
 ROOF DRAINS. GIVE CALCULATIONS AND SIZE
 PER SPC-94 SECTION 1108.5 & FIG 1109.3.
 (14) SHEET C-1, FIRE AND IRRIGATION BACK
 FLOW PREVENTERS NOT SHOWN. SEE COMMENT
 #5 OF PLAN REVIEW DATED 7-15-01.
 (15) PAGES P002, P201, & P401. INFORMAT-
 ION STILL REQUIRED FOR GAS PERMIT APPLI-
 CATION. #1 TYPE OF MATERIAL, #2 TYPE OF
 GAS & #3 MANUFACTURE INFORMATION FOR GAS
 BOILER.
 (16) PAGE P201 PLEASE PROVIDE A CONDEN-
 SATE RISER DIAGRAM WITH PIPE SIZES AND
 SHOW LOAD OF EACH NUMBERED RISER.
 (17) PAGE P203 PLEASE PROVIDE A RISER
 DIAGRAM WITH PIPE SIZE FOR TRENCH DRAINS
 FOR THE FOURTH AND FIFTH FLOOR PARKING
 GARAGE.
 (18) PAGE P401 GAS RISER DIAGRAM. ARE
 ALL 4 SHUT OFF VALVES NECESSARY?
 (19) PAGE P301 FLOOR DRAINS AT THE WATER
 CLOSETS, ARE ALL THESE NECESSARY?
 (20) PAGES P203 & P204, KEY NOTES #2.
 PLEASE CHANGE TO REFLECT CHANGE ON P205
 SAME NOTE.
  
 REVIEW BY KEN STEVENS