2001-09-18 00:00:00*******************DENIED***************
  
  
 1.THERE SHALL BE NO RECIRCULATION OF
 AIR IN THE TRUCK LOADING AREA, PLAN
 AC-2.EXHAUST SHALL TERMINATE TO
 OUTDOORS, 1997 SMC 1105.7.2 AND
 SECTION 506.1.OUTSIDE AIR SHALL
 BE BROUGHT IN FROM OUTDOORS AND NOT
 FROM THE TRUCK LOADING AREA, RISK
 OF CARBON MONOXIDE BEING TRANSFERED
 INTO THESE SPACES.
  
 2.PLEASE PROVIDE SEQUENCE OF
 OPERATION SHOWING COMPLIANCE WITH
 CHAPTER 11 SECTION 1105.7.4 FOR
 NORMAL VENTILATION AND SECTION
 1105.7.5 FOR EMERGENCY OPERATION.
  
 3.SIGNS SHALL BE POSTED AT CHILLER
 ROOM DOORS PROHIBITING ACCESS OF
 UNAUTHORIZED PERSONNEL.
  
 4.BOTH BREATHING APPARATUS SHALL BE
 LOCATED OUTSIDE OF THE CHILLER
 ROOM.
  
 5.ALARM/STROBE SHALL BE LOCATED IN
 SUCH A MANNER THAT ALL ENTRANCES
 WILL HAVE NOTIFICATION OF A
 HAZARDOUS SITUATION.
  
 6.PLAN SHEET INDICATES A REFRIGERANT
 SENSOR OUTSIDE THE CHILLER ROOM.
 WHAT PURPOSE DOES IT SERVE?
  
 7.REFRIGERANT SENSORS SHALL BE
 LOCATED IN CLOSE PROXIMITY TO THE
 EQUIPMENT.PLAN SHEET AC-7 SENSORS
 ARE LOCATED NEXT TO DOORS AND
 AN EXHAUST FAN, THIS MAY HAVE AN
 ADVERSE EFFECT ON THE SENSORS.
  
 8.FAN COIL ACCESS MUST BE ADEQUATE
 FOR SERVICE, CLEANING AND REMOVAL.
  
 NOTE:UNDER THE 1998 FAIR HOUSING ACT
 PART TWO CHAPTER 5, THERMOSTATS
 AND OTHER CONTROLS THAT MUST BE
 READ ARE MOUNTED AT OR LOWER THAN
 48" ABOVE THE FLOOR.
  