2001-08-29 00:00:001) PLEASE INDICATE DISTANCES FROM STAIR
 # 1 AND # 4 TO THE ADJACENT BUILDING,
 TRANSFORMERS, OBSTACLES, ETC.
 2) GENERATOR ROOM TO BE AT LEAST TWO
 HOUR FIRE RATED.
 3) EMERGENCY LIGHTING REQUIRED IN FIRE
 PUMP ROOM.
 4) HOW IS COMBUSTIBLE LINT REMOVED FROM
 DRYER RISER.
 5) FIRE DAMPERS TO COMPLY WITH UL 555.
 6) PLEASE SHOW DIMENSION OF WALL AND
 RAILING FOR BALCONIES.
  