| Notes |
| Date |
Text |
| 2001-08-29 00:00:00 | 1) PLEASE INDICATE DISTANCES FROM STAIR | | | # 1 AND # 4 TO THE ADJACENT BUILDING, | | | TRANSFORMERS, OBSTACLES, ETC. | | | 2) GENERATOR ROOM TO BE AT LEAST TWO | | | HOUR FIRE RATED. | | | 3) EMERGENCY LIGHTING REQUIRED IN FIRE | | | PUMP ROOM. | | | 4) HOW IS COMBUSTIBLE LINT REMOVED FROM | | | DRYER RISER. | | | 5) FIRE DAMPERS TO COMPLY WITH UL 555. | | | 6) PLEASE SHOW DIMENSION OF WALL AND | | | RAILING FOR BALCONIES. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|