Plan Review Notes
Plan Review Notes For Permit 01070072
Permit Number 01070072
Review Stop P
Sequence Number 1
Notes
Date Text
2001-07-15 00:00:00PLUMBING PLAN REVIEW, DENIED.
 FAIR HOUSING ACT,24 (CFR) 100.205(C)(IV)
 REVISED APRIL 1998,DESIGN MANUAL
 CODE REFERENCES FACBC-97,SPC-94,SGC-97
 (1)SHT A-201 PANTRY RM #1-011, SINK TO
 COMPLY FACBC W/SEC 4.24.1 HEIGHT 34" FF.
 (2)SHT A-201,DIRECTORS APT RM# 1-009A,
 NOT SHOWN ON SHT A-302,FAIR HOUSING ACT
 ADAPTABILITY PLAN.
 (3A) SHT A-302 DETAIL 7, 20 GA SHEET
 METAL DOES NOT MEET THE GUIDE LINES FOR
 INSTALLATION OF GRABS,SEE APPEX-A,PG.A3
 (3B) CLEAR FLOOR SPACE AND DOOR SWING IS
 REQUIRED AT TIME OF CONSTRUCTION, WALLS
 AND DOORS ARE NOT TO BE ALTERED, AFTER
 THE COMPLETION OF CONSTRUCTION. SEE PG.
 7.39 MANEUVERING SPACE IN BATH ROOMS.
 BATH TUB CLEAR FLR SPACE AT CONTROL END.
 (3C) SHOW ALL DIMENSIONS FOR CLEAR FLOOR
 SPACE ON ARCHITECTURAL PLANS,SEE DESIGN
 MANUAL. INCLUDE REQUIRMENTS IN CHAPT. 5
 ELECTRICAL OUTLETS, CONTROLS.
 (4)SHT A-208 PRIMARY ROOF DRAINS, CALCUL
 ATIONS FOR ROOF DRAINS,INCLUDE HALF THE
 VERTICAL WALLS (PARAPET WALLS) AND UPPER
 ROOFS,DRAINING DOWN ON MAIN ROOF.
 SECONDARY DRAINS,SEC 1108.5,FIG.1109.3
 RAIN FALL RATE, CALCULATIONS AND SIZE.
 (5) SHT C-1 SHOW LOCATION OF BACK FLOW
 PREVENTERS,IRRIGATION,FIRE,DOMESTIC
 WATER, ALSO SANITARY SEWER TIE INS.
 (6)SHT P-201,204,SEE ATTACHED GAS PERMIT
 APPLICATION REQUIRMENTS, ADDRESS EA ITEM
 (7) SHT P-201 TO P-206, SEC 104.3 PLANS
 PROVIDE A ISOMETRIC DRAWING OF DWV,RWL
 RISERS THRU THE ROOF, NUMBER EA RISER,
 SIZE AND LOAD, REQUIRED.
 (8A) SHT P-201 ELECTRICAL RM # 1-107
 DRAIN PAN OVER ELECTRICAL EQUIPMENT.
 NEC-99, ART.1010-26 PANNEL HEAD RM.
 (8B) MECHANICAL RM # 1-019 WATER HEATER
 IN CEILING, SEC 501.7,READLY ACCESSIBLE.
 PROVIDE A DETAIL OF A WORKING PLATFORM
 WITH A SHIPS LADDER,FIXED IN PLACE, OR
 RELOCATE TO FLOOR LEVEL.
 (8C) RESIDENT DIRECTOR APT.# 1-009A, NO
 DWV AND WATER PIPING SHOWN FOR THIS UNIT
 (8C) TRUCK BAY RM # 1-020, TRENCH DRAINS
 SHALL BE CONNECTED TO STORM DRAIN.
 (9)SHT P-205,206 NOTE (2) A/C CONDENSATE
 TO TERMINATE IN 5TH FLR CEILING, VENT AT
 HIGHEST POINT.SPC-94 AMENDMENTS TO MODEL
 CNTY.WIDE PLBG CODE,SEC 804.3(5). (VTR)
 (10) SHT P-301 FIXTURE WATER PIPING,
 SEC 607.7, AMENDMENTS TO MODEL CNTY.WIDE
 PLBG CODE,NO MORE THAN 2 FIXTURES ON 1/2
 COLD WATER, NO MORE THAN 4 FIXTURES ON
 1/2" HOT WATER. SUITES A,B,C,,E.
 (11) SHT 401, WATER HAMMER ARRESTORS TO
 BE INSTALLED AS PER MANFACTURE INSTRUCT-
 IONS, NOT AT THE HIGH POINT. USE WATER
 HAMMER ARRESTOR STD PDI-201 FOR PLACE-
 MENT AND SIZE.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096X8233