| 2001-07-15 00:00:00 | PLUMBING PLAN REVIEW, DENIED. |
| | FAIR HOUSING ACT,24 (CFR) 100.205(C)(IV) |
| | REVISED APRIL 1998,DESIGN MANUAL |
| | CODE REFERENCES FACBC-97,SPC-94,SGC-97 |
| | (1)SHT A-201 PANTRY RM #1-011, SINK TO |
| | COMPLY FACBC W/SEC 4.24.1 HEIGHT 34" FF. |
| | (2)SHT A-201,DIRECTORS APT RM# 1-009A, |
| | NOT SHOWN ON SHT A-302,FAIR HOUSING ACT |
| | ADAPTABILITY PLAN. |
| | (3A) SHT A-302 DETAIL 7, 20 GA SHEET |
| | METAL DOES NOT MEET THE GUIDE LINES FOR |
| | INSTALLATION OF GRABS,SEE APPEX-A,PG.A3 |
| | (3B) CLEAR FLOOR SPACE AND DOOR SWING IS |
| | REQUIRED AT TIME OF CONSTRUCTION, WALLS |
| | AND DOORS ARE NOT TO BE ALTERED, AFTER |
| | THE COMPLETION OF CONSTRUCTION. SEE PG. |
| | 7.39 MANEUVERING SPACE IN BATH ROOMS. |
| | BATH TUB CLEAR FLR SPACE AT CONTROL END. |
| | (3C) SHOW ALL DIMENSIONS FOR CLEAR FLOOR |
| | SPACE ON ARCHITECTURAL PLANS,SEE DESIGN |
| | MANUAL. INCLUDE REQUIRMENTS IN CHAPT. 5 |
| | ELECTRICAL OUTLETS, CONTROLS. |
| | (4)SHT A-208 PRIMARY ROOF DRAINS, CALCUL |
| | ATIONS FOR ROOF DRAINS,INCLUDE HALF THE |
| | VERTICAL WALLS (PARAPET WALLS) AND UPPER |
| | ROOFS,DRAINING DOWN ON MAIN ROOF. |
| | SECONDARY DRAINS,SEC 1108.5,FIG.1109.3 |
| | RAIN FALL RATE, CALCULATIONS AND SIZE. |
| | (5) SHT C-1 SHOW LOCATION OF BACK FLOW |
| | PREVENTERS,IRRIGATION,FIRE,DOMESTIC |
| | WATER, ALSO SANITARY SEWER TIE INS. |
| | (6)SHT P-201,204,SEE ATTACHED GAS PERMIT |
| | APPLICATION REQUIRMENTS, ADDRESS EA ITEM |
| | (7) SHT P-201 TO P-206, SEC 104.3 PLANS |
| | PROVIDE A ISOMETRIC DRAWING OF DWV,RWL |
| | RISERS THRU THE ROOF, NUMBER EA RISER, |
| | SIZE AND LOAD, REQUIRED. |
| | (8A) SHT P-201 ELECTRICAL RM # 1-107 |
| | DRAIN PAN OVER ELECTRICAL EQUIPMENT. |
| | NEC-99, ART.1010-26 PANNEL HEAD RM. |
| | (8B) MECHANICAL RM # 1-019 WATER HEATER |
| | IN CEILING, SEC 501.7,READLY ACCESSIBLE. |
| | PROVIDE A DETAIL OF A WORKING PLATFORM |
| | WITH A SHIPS LADDER,FIXED IN PLACE, OR |
| | RELOCATE TO FLOOR LEVEL. |
| | (8C) RESIDENT DIRECTOR APT.# 1-009A, NO |
| | DWV AND WATER PIPING SHOWN FOR THIS UNIT |
| | (8C) TRUCK BAY RM # 1-020, TRENCH DRAINS |
| | SHALL BE CONNECTED TO STORM DRAIN. |
| | (9)SHT P-205,206 NOTE (2) A/C CONDENSATE |
| | TO TERMINATE IN 5TH FLR CEILING, VENT AT |
| | HIGHEST POINT.SPC-94 AMENDMENTS TO MODEL |
| | CNTY.WIDE PLBG CODE,SEC 804.3(5). (VTR) |
| | (10) SHT P-301 FIXTURE WATER PIPING, |
| | SEC 607.7, AMENDMENTS TO MODEL CNTY.WIDE |
| | PLBG CODE,NO MORE THAN 2 FIXTURES ON 1/2 |
| | COLD WATER, NO MORE THAN 4 FIXTURES ON |
| | 1/2" HOT WATER. SUITES A,B,C,,E. |
| | (11) SHT 401, WATER HAMMER ARRESTORS TO |
| | BE INSTALLED AS PER MANFACTURE INSTRUCT- |
| | IONS, NOT AT THE HIGH POINT. USE WATER |
| | HAMMER ARRESTOR STD PDI-201 FOR PLACE- |
| | MENT AND SIZE. |
| | END OF COMMENTS PAUL SCHMITZ |