Plan Review Notes
Plan Review Notes For Permit 01070072
Permit Number 01070072
Review Stop M
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 CHILLER ROOM SHALL COMPLY WITH CHAPTER
 11 OF THE 1997 SMC.
  
 1.REFRIGERANT DETECTOR SHALL BE TIED
 TO AN ALARM/STROBE.
  
 2.ALARM/STROBE SHALL BE LOCATED OUT-
 SIDE OF CHILLER ROOM ENTRANCE AS
 WELL AS INSIDE. ALL ALARM/STROBES
 MUST BE IDENTIFIED ON THE PLAN.
  
 3.SIGNS SHALL BE POSTED AT CHILLER
 ROOM DOORS PROHIBITING ACCESS OF
 UNAUTHORIZED PERSONNEL.
  
 4.PLEASE DESCRIBE VENTILATION FOR
 CHILLER ROOM BOTH NORMAL AND
 EMERGENCY SITUATIONS.
  
 5.BREATHING APPARATUS SHALL BE
 LOCATED OUTSIDE CHILLER ROOM AT
 A LOCATION CONVENIENT TO CHILLER
 ROOM.
  
 6.TERMINATION OF RELIEF DEVICES SHALL
 BE OUTSIDED AND A MINIMUM OF 15 FT
 ABOVE THE ADJOINING GRADE LEVEL AND
 20 FT FROM ANY WINDOW, AIR INTAKE,
 OR EXIT TO ANY BUILING.
  
 7.CONDENSATE DRAIN LINES NEED TO BE
 IDENTIFIED ON PLAN.
  
 8.DRYER VENTS ARE BE RUN TO THE
 ATMOSPHERE INDIVIDUALLY IN SHAFT.
  
 9.FAN COIL ACCESS MUST BE ADEQUATE
 FOR SERVICE, CLEANING, AND REMOVAL.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved