| Date |
Text |
| 2001-08-02 00:00:00 | ******************DENIED**************** |
| | |
| | |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW: |
| | |
| | CHILLER ROOM SHALL COMPLY WITH CHAPTER |
| | 11 OF THE 1997 SMC. |
| | |
| | 1.REFRIGERANT DETECTOR SHALL BE TIED |
| | TO AN ALARM/STROBE. |
| | |
| | 2.ALARM/STROBE SHALL BE LOCATED OUT- |
| | SIDE OF CHILLER ROOM ENTRANCE AS |
| | WELL AS INSIDE. ALL ALARM/STROBES |
| | MUST BE IDENTIFIED ON THE PLAN. |
| | |
| | 3.SIGNS SHALL BE POSTED AT CHILLER |
| | ROOM DOORS PROHIBITING ACCESS OF |
| | UNAUTHORIZED PERSONNEL. |
| | |
| | 4.PLEASE DESCRIBE VENTILATION FOR |
| | CHILLER ROOM BOTH NORMAL AND |
| | EMERGENCY SITUATIONS. |
| | |
| | 5.BREATHING APPARATUS SHALL BE |
| | LOCATED OUTSIDE CHILLER ROOM AT |
| | A LOCATION CONVENIENT TO CHILLER |
| | ROOM. |
| | |
| | 6.TERMINATION OF RELIEF DEVICES SHALL |
| | BE OUTSIDED AND A MINIMUM OF 15 FT |
| | ABOVE THE ADJOINING GRADE LEVEL AND |
| | 20 FT FROM ANY WINDOW, AIR INTAKE, |
| | OR EXIT TO ANY BUILING. |
| | |
| | 7.CONDENSATE DRAIN LINES NEED TO BE |
| | IDENTIFIED ON PLAN. |
| | |
| | 8.DRYER VENTS ARE BE RUN TO THE |
| | ATMOSPHERE INDIVIDUALLY IN SHAFT. |
| | |
| | 9.FAN COIL ACCESS MUST BE ADEQUATE |
| | FOR SERVICE, CLEANING, AND REMOVAL. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT |
| | PATTY KRAUSS AT 659-8096 EXT. 8388. |