Plan Review Notes
Plan Review Notes For Permit 01070072
Permit Number 01070072
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-07-05 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) PLEASE EXPLAIN 1-003 UNDER RAMP
 STORAGE.
 3) PLEASE PROVIDE EVIDENCE OF COMPLIANCE
 WITH STANDARD BUILDING CODE, SECTION
 3003.4 STRETCHER REQUIREMENTS.
 4) PLEASE EXPLAIN ROOMS 6-011 AND 6-012
 TRASH.
 5) PLEASE PROVIDE PRODUCT APPROVALS FOR
 THE FOUR ROLLING FIRE SHUTTERS.
 6) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS OF BUILDING.
 7) PRIOR TO OCCUPANCY ALL UNFINSHED
 AREAS OF THE BUILDING ARE TO MEET ALL
 MINIMUM LIFE SAFETY REQUIREMENTS.
 8) ADDITIONAL ILLUMINATED EXIT SIGNS
 APPEAR TO BE NEEDED ON THE SECOND,
 THIRD, AND FOURTH FLOOR GARAGE LIGHTING
 PLANS. PLEASE CLEARLY IDENTIFY EMERGENCY
 LIGHT FIXTURES ON GARAGE FLOORS.
 9) PLEASE EXPLAIN SMOKE DETECTOR NOTE
 ON PAGE E404.
 10) NO SMOKE DETECTORS SHOWN IN
 ELEVATOR LOBBIES 6-010 AND 6-013.
 11) PLEASE PROVIDE MORE DETAILS ON
 DIESEL GENERATOR.PRODUCT APPROVALS
 REQUIRED FOR GENERATOR AND DIESEL TANK.
 12) PLEASE PROVIDE EXIT DISCHARGE
 DISTANCES FROM STAIR # 1 AND # 4 TO
 BAXTER HALL OR TO ANY EQUIPMENT
 ASSOCIATED WITH IT.
 13) DOES THE NEW BUILDING BLOCK OR
 OBSCURE ANY EXISTING FIRE PROTECTION
 EQUIPMENT OR DEVICES FOR BAXTER HALL.
 14) PLEASE PROVIDE CODE REFERENCE THAT
 ALLOWS NO FIRE PROTECTION FOR COOLING
 TOWER.
 15) DOES THE EXHAUST FANS RUN
 CONTINOUSLY IN THE GARAGE.
 16) PROVIDE MORE DETAILS ON RAILINGS
 AT DORM BALCONIES.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910