| 2001-07-05 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY |
| | CODE 3343-00. |
| | 2) PLEASE EXPLAIN 1-003 UNDER RAMP |
| | STORAGE. |
| | 3) PLEASE PROVIDE EVIDENCE OF COMPLIANCE |
| | WITH STANDARD BUILDING CODE, SECTION |
| | 3003.4 STRETCHER REQUIREMENTS. |
| | 4) PLEASE EXPLAIN ROOMS 6-011 AND 6-012 |
| | TRASH. |
| | 5) PLEASE PROVIDE PRODUCT APPROVALS FOR |
| | THE FOUR ROLLING FIRE SHUTTERS. |
| | 6) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR WALLS |
| | AND CEILINGS OF BUILDING. |
| | 7) PRIOR TO OCCUPANCY ALL UNFINSHED |
| | AREAS OF THE BUILDING ARE TO MEET ALL |
| | MINIMUM LIFE SAFETY REQUIREMENTS. |
| | 8) ADDITIONAL ILLUMINATED EXIT SIGNS |
| | APPEAR TO BE NEEDED ON THE SECOND, |
| | THIRD, AND FOURTH FLOOR GARAGE LIGHTING |
| | PLANS. PLEASE CLEARLY IDENTIFY EMERGENCY |
| | LIGHT FIXTURES ON GARAGE FLOORS. |
| | 9) PLEASE EXPLAIN SMOKE DETECTOR NOTE |
| | ON PAGE E404. |
| | 10) NO SMOKE DETECTORS SHOWN IN |
| | ELEVATOR LOBBIES 6-010 AND 6-013. |
| | 11) PLEASE PROVIDE MORE DETAILS ON |
| | DIESEL GENERATOR.PRODUCT APPROVALS |
| | REQUIRED FOR GENERATOR AND DIESEL TANK. |
| | 12) PLEASE PROVIDE EXIT DISCHARGE |
| | DISTANCES FROM STAIR # 1 AND # 4 TO |
| | BAXTER HALL OR TO ANY EQUIPMENT |
| | ASSOCIATED WITH IT. |
| | 13) DOES THE NEW BUILDING BLOCK OR |
| | OBSCURE ANY EXISTING FIRE PROTECTION |
| | EQUIPMENT OR DEVICES FOR BAXTER HALL. |
| | 14) PLEASE PROVIDE CODE REFERENCE THAT |
| | ALLOWS NO FIRE PROTECTION FOR COOLING |
| | TOWER. |
| | 15) DOES THE EXHAUST FANS RUN |
| | CONTINOUSLY IN THE GARAGE. |
| | 16) PROVIDE MORE DETAILS ON RAILINGS |
| | AT DORM BALCONIES. |
| | |