Plan Review Notes
Plan Review Notes For Permit 01070072
Permit Number 01070072
Review Stop E
Sequence Number 1
Notes
Date Text
2001-07-31 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT NO GFI PROTECT-
 -ION OF MDP AND MCC IS SHOWN. PLEASE
 NOTE THAT 230-95 REQ`SPROTECTION
 FOR 1000A`S OR MORE OVER 150V TO GRND.
  
 2)NOTE: PLEASE NOTE THAT CONDUCTOR FEED-
 ING MDP DO NOT MEET 240-3-C. PLEASE
 NOTE THAT CONDUCTORS ARE TO BE SIZED
 PER 310-16 75'COL. PER 110-14
  
 3)NOTE: PLEASE CLARIFY OCP IN MOTOR
 CONTRLOLLER PER 695-3-1, PLEASE ASLO
 NOTE GROUPING OF DISCS REFERENCED BY
 SAME ART TO 230-72B. PLEASE SEE 695-4B-1
 PLEASE SUBMIT CODE LETTER OF MOTOR.
 4)NOTE: PLEASE PROVIDE CLARIFICATION
 OF DISCONNECTINGS MEANS OF GENERATOR
 GROUPED WITH MAIN PER 230-70 AND 230-72.
 PLEASE NOTE THAT MUST MEET 230-76 AND
 230-79.
  
 5)NOTE: PLEASE NOTE THAT GROUNDING
 ELECTRODE SYSTEM WAS NOT SUBMITTED ON
 ONE LINE DIAGRAM. PLEASE SUBMIT.
 PER 250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372