| Plan Review Notes For Permit 01070072 |
| Permit Number |
01070072 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-31 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT NO GFI PROTECT- | | | -ION OF MDP AND MCC IS SHOWN. PLEASE | | | NOTE THAT 230-95 REQ`SPROTECTION | | | FOR 1000A`S OR MORE OVER 150V TO GRND. | | | | | | 2)NOTE: PLEASE NOTE THAT CONDUCTOR FEED- | | | ING MDP DO NOT MEET 240-3-C. PLEASE | | | NOTE THAT CONDUCTORS ARE TO BE SIZED | | | PER 310-16 75'COL. PER 110-14 | | | | | | 3)NOTE: PLEASE CLARIFY OCP IN MOTOR | | | CONTRLOLLER PER 695-3-1, PLEASE ASLO | | | NOTE GROUPING OF DISCS REFERENCED BY | | | SAME ART TO 230-72B. PLEASE SEE 695-4B-1 | | | PLEASE SUBMIT CODE LETTER OF MOTOR. | | | 4)NOTE: PLEASE PROVIDE CLARIFICATION | | | OF DISCONNECTINGS MEANS OF GENERATOR | | | GROUPED WITH MAIN PER 230-70 AND 230-72. | | | PLEASE NOTE THAT MUST MEET 230-76 AND | | | 230-79. | | | | | | 5)NOTE: PLEASE NOTE THAT GROUNDING | | | ELECTRODE SYSTEM WAS NOT SUBMITTED ON | | | ONE LINE DIAGRAM. PLEASE SUBMIT. | | | PER 250-50 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|