| 2001-07-30 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01070072 |
| | 1000 S DIXIE HWY |
| | FINFROCK CONSTRUCTION |
| | (407) 293-4000 |
| | |
| | SBC = STANDARD BUILDING CODE 1997 EDI. |
| | SBC* = 1997 AMENDMENTS STANDARD BUILDING |
| | CODE |
| | 1)- SHEET A-803 NOTES 1 & 2 GLAZED OPEN- |
| | INGS ARE TO MEET THE STANDARD BUILDING |
| | CODE STANDARD FOR DETERMINING IMPACT |
| | RESISTANCE FROM WINDBORNE DEBRIS, SEE |
| | SSTD-12-97. THE CITY DOES ACCEPT THE |
| | DADE COUNTY PRODUCT APPROVAL. |
| | |
| | 2)- FL ACCESSIBILITY CODE 4.6.4: |
| | SIGNAGE FOR HANDICAPPED VANS. |
| | |
| | 3)- SHEET A-C 9 SIZE OF BOILER? SBC 704. |
| | 1.3.3.3. |
| | |
| | 4)_ SHEET A-302 DETAILS 3,5 & 6 ALL |
| | DETAILS INDICATE A SOLID BLUE LINE, IS |
| | THIS A VOID FOR UTILITIES? |
| | |
| | 5)- SHEET A-302 THE DETAILS INDICATE |
| | THERE IS A LAUNDRY WITH DRYERS, MISSING |
| | |
| | INFORMATION ON THE CHASE FORTHE DRYER |
| | VENTS? |
| | |
| | 6)- SHEET A-504 SEC. A INDICATES THERE |
| | WILL BE ROOF SHEATHING, THE PLANS DO |
| | NOT INDICATE WHAT TYPE OF SHEATHING IS |
| | TO BE USED, THICKNESS, ETC. |
| | |
| | 7)- ROOM 1-003 UNDER RAMP STORAGE: |
| | 2,740 SQ FT & TRAVEL DISTANCE 80',THE |
| | SBC 1027.1.1 SINGLE EXIT REQUIREMENTS: |
| | 2500 MAX SQ FT, TRAVEL DISTANCE NOT TO |
| | EXCEED 50'. |
| | |
| | 8)- SBC 411.3 OPEN PARKING GARAGE : SHOW |
| | CALCULATIONS FOR OPEN WALL AREA, DETER- |
| | MINATION METHOD #1 OR #2. |
| | |
| | 9)- STRUCTURAL DRAWINGS ARE NOT COMPLETE |
| | THEY DO NOT SHOW DETAILS PAST THE FIRST |
| | FLOOR, MISSING WELDING INFORMATION FOR |
| | CONNECTING PLATES, LOCATION, DIRECTION |
| | AND MAGNITUDE OF LOADS TO BE RESISTED. |
| | |
| | 10)- SBC 1606.4.1 /1707.4.1 THE CODE |
| | REQUIRES GLAZED OPENINGS TO HAVE LARGE |
| | MISSLE TESTING,PRODUCT TESTING REPORTS |
| | ARE REQUIRED TO SHOW COMPLIANCE, A NOTE |
| | ON THE DRAWINGS INDICATING WHAT WILL BE |
| | DONE DOES SHOW INTENT, A PROVISO CAN BE |
| | WRITTEN FOR THIS SECTION OF THE CODE. |
| | SINCE THE WINDOWS AND DOORS WOULD BE RE- |
| | VIEWED AT A LATER DATE THEYWOULD BE |
| | UNDER A SEPERATE PERMIT WITH ASSOCIATED |
| | FEES. |
| | |
| | 11)- SBC 1606.2.6.2/ 1707.5 CLAY TILE & |
| | CEMENT TILE WILL ALSO REQUIRE THE PRODUC |
| | T TESTING REPORTS (2 COPIES REQUIRED) |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X 8412 |