| Plan Review Notes For Permit 01070019 |
| Permit Number |
01070019 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-24 00:00:00 | ********************DENIED************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMAITON | | | FOR MECHANICAL REVIEW: | | | | | | | | | 1.DUCT MATERIAL, SIZE AND ROUTING OF | | | DUCT WORK. | | | | | | 2.SIZE OF GRILLS & CFM DISTRIBUTION. | | | | | | 3.LOCATION OF RETURN AIR.NOTE, AREAS | | | WITH GREATER THAN 300 CFM REQUIRE | | | A RETURN AIR.SHOULD SPACE ABOVE | | | THE CEILING BE A RETURN AIR PLENUM, | | | NO COMBUSTIBLES ARE ALLOWED. | | | | | | IF YOU HAVE ANY QUESITONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|