Plan Review Notes
Plan Review Notes For Permit 01061375
Permit Number 01061375
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-07-05 00:00:001) NO MASTER PERMIT HAS BEEN ISSUED FOR
 THE NEXTEL SITE. EXISTING PROBLEMS WITH
 CONDUITS HAVING BEEN RUN THROUGH A RATED
 STAIRWAY HAS NOT ALLOWED THE PERMIT TO
 BE ISSUED. IT IS NOT KNOWN WHEN A PERMIT
 WILL BE ISSUED FOR THIS SITE SO
 INSTALLATION OF THE SUPPRESSION SYSTEM
 IS DONE AT THE CONTRACTORS RISK.
 2) FM 200 SYSTEM IS NOT BE USED IN
 LIEU OF REQUIRED FIRE SPRINKLER
 PROTECTION FOR THE BUILDING.
 3) AFTER INSTALLATION SYSTEM IS TO BE
 INSPECTED WITH FIRE AND MECHANICAL
 INSPECTORS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910