| Plan Review Notes For Permit 01061355 |
| Permit Number |
01061355 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-07-24 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01061355 | | | ADDRESS: 3230 COMMERCE PLACE | | | SUITE : "A" | | | CONT: PDC DEVELOPMENT CORP | | | TEL: (561) 793-5852 | | | | | | SECOND REQUEST ADD INFO: | | | 1)- PROVIDE THE TEST DATA AND OR REPORTS | | | FOR THE NEW WINDOWS AND GLASS / ALUM | | | DOOR. SBC AMEND 1606.4.1/ 1707.4.1 | | | SBCCI OR DADE COUNTY PRODUCT APPROVAL | | | REPORT ARE REQUIRED. | | | 2)- SBC 1606.2.6.2:COMPONENTS & CLADDING | | | SHOW WINDOW & DOOR BUCK DETAIL ATTACH- | | | MENT. | | | 3)- SBC 1606.2.6.2: SHOW THE DESIGN PRES | | | SURES FOR THE NEW WINDOWS & DOOR. | | | 4)- SBC 104.2.2* HOW WILL THE I HR. | | | RATED WALL (UL# U 465), HOW WILL THE | | | DRYWALL BE ATTACHED TO THE STUDS WHEN | | | THE WALL STANDS NEXT TO AN EXISTING WALL | | | ALSO HOW WILL THE JOINT TAPE AND COM- | | | POUND BE APPLIED TO THE SIDE ADJACENT TO | | | THE EXISTING WALL? | | | 5)- HIGHLIGHT THE WORK SPECIFICIALLY, | | | WHAT PORTION OF WORK SHOWN ON THE PLAN | | | IS INTENDED TO BE ACCOMPLISHED FOR THE | | | DECLARED VALUE OF $12,000.00UNDER THIS | | | PERMIT APPLICATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|