Plan Review Notes
Plan Review Notes For Permit 01061314
Permit Number 01061314
Review Stop P
Sequence Number 1
Notes
Date Text
2001-07-07 00:00:00DENIED;
  
 1.COVER PAGE (CONSTRUCTION DATA).
 PLUMBING CODE SHOULD BE 1994 ADDITION
 OF THE STANDARD PLUMBING CODE.
  
 2.PAGE MEP 1 DIAGRAM #3 BALL VALVES ARE
 REQUIRED IN PLACE OF GATE VALVES.
  
 3.PAGE MEP 1 MEP NOTE #5 BACKFLOW
 PREVENTER NOT PERMITED TO BE INSTALLED
 IN ELECTRICAL ROOM.
  
 4.PAGE SPI NOTE 2.07 CONSTRUCTION WATER
 SHALL HAVE BACKFLOW PROTECTION.
  
 5.CANOPY;
 A.SHOW SQUIRE FOOTAGE AND CALCULATE
 RAINFALL FOR EACH GUTTER AND DOWN
 SPOUT.
 B. SIZE PER. CHAPTER 11 94 SPC.
 C.SHOW PIPING TO EXISTING STORM
 SEWER SYSTEM PER.1101.2
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369