| Plan Review Notes For Permit 01061314 |
| Permit Number |
01061314 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-07 00:00:00 | DENIED; | | | | | | 1.COVER PAGE (CONSTRUCTION DATA). | | | PLUMBING CODE SHOULD BE 1994 ADDITION | | | OF THE STANDARD PLUMBING CODE. | | | | | | 2.PAGE MEP 1 DIAGRAM #3 BALL VALVES ARE | | | REQUIRED IN PLACE OF GATE VALVES. | | | | | | 3.PAGE MEP 1 MEP NOTE #5 BACKFLOW | | | PREVENTER NOT PERMITED TO BE INSTALLED | | | IN ELECTRICAL ROOM. | | | | | | 4.PAGE SPI NOTE 2.07 CONSTRUCTION WATER | | | SHALL HAVE BACKFLOW PROTECTION. | | | | | | 5.CANOPY; | | | A.SHOW SQUIRE FOOTAGE AND CALCULATE | | | RAINFALL FOR EACH GUTTER AND DOWN | | | SPOUT. | | | B. SIZE PER. CHAPTER 11 94 SPC. | | | C.SHOW PIPING TO EXISTING STORM | | | SEWER SYSTEM PER.1101.2 | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|