Plan Review Notes
Plan Review Notes For Permit 01061314
Permit Number 01061314
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-07-05 00:00:001) UNDERGROUND FUEL TANKS TO COMPLY
 WITH NFPA 30, THE STANDARD FOR
 FLAMMABLE AND COMBUSTIBLE LIQUIDS
 CODE.
 2) COMPLIANCE IS REQUIRED WITH CITY
 CODE SECTIONS 11-70 AND 11-71 WITH
 REGARDS TO DEPTH OF COVERAGE OF FUEL
 TANKS AND VENT PIPES FOR THESE TANKS.
 3) FUEL DISPENSING HOSES SHALL BE LISTED
 AND BE NO LONGER THAN 18 FEET LONG.
 4) PLEASE INDICATE BREAKAWAY LOCATIONS.
 5) PLEASE INDICATE TYPES OF FIRE
 EXTINGUISHERS PLANNED FOR USE.
 6) PLEASE CLEARLY IDENTIFY DISTANCES
 FROM UNDERGROUND TANKS TO PROPERTY
 LINES AND ADJACENT BUILDINGS.
 7) ALL DISPENSING DEVICES ARE TO BE
 APPROVED FOR USE.
 8) PLEASE INDICATE THE DISTANCES
 BETWEEN THE UNDERGOUND FUEL TANKS.
 9) THE REMOVABLE SIGN TO INDICATE
 SITE SHOULD BE PERMANANT TO PREVENT
 VANDALISM OR THEFT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910