| Notes |
| Date |
Text |
| 2001-07-05 00:00:00 | 1) UNDERGROUND FUEL TANKS TO COMPLY | | | WITH NFPA 30, THE STANDARD FOR | | | FLAMMABLE AND COMBUSTIBLE LIQUIDS | | | CODE. | | | 2) COMPLIANCE IS REQUIRED WITH CITY | | | CODE SECTIONS 11-70 AND 11-71 WITH | | | REGARDS TO DEPTH OF COVERAGE OF FUEL | | | TANKS AND VENT PIPES FOR THESE TANKS. | | | 3) FUEL DISPENSING HOSES SHALL BE LISTED | | | AND BE NO LONGER THAN 18 FEET LONG. | | | 4) PLEASE INDICATE BREAKAWAY LOCATIONS. | | | 5) PLEASE INDICATE TYPES OF FIRE | | | EXTINGUISHERS PLANNED FOR USE. | | | 6) PLEASE CLEARLY IDENTIFY DISTANCES | | | FROM UNDERGROUND TANKS TO PROPERTY | | | LINES AND ADJACENT BUILDINGS. | | | 7) ALL DISPENSING DEVICES ARE TO BE | | | APPROVED FOR USE. | | | 8) PLEASE INDICATE THE DISTANCES | | | BETWEEN THE UNDERGOUND FUEL TANKS. | | | 9) THE REMOVABLE SIGN TO INDICATE | | | SITE SHOULD BE PERMANANT TO PREVENT | | | VANDALISM OR THEFT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|