Plan Review Notes
Plan Review Notes For Permit 01061304
Permit Number 01061304
Review Stop B
Sequence Number 3
Notes
Date Text
2002-04-22 00:00:00THE STAIR AND PLATFORM SHOP DRAWINGS
 PREPARED BY RON UPHOFF, ARCH. HAVE
 INADEQUATE INFORMATION.
  
 THE STAIR RISERS SHOWN AS 8.43" DO NOT
 COMPLY WITH SBC 1007.3.1.
  
 THE 1" PIPE DOES NOT COMPLY WITH SBC
 1007.5.3.SEE ALSO 1022.4.
  
 SEE SBC 1007.5.5 FOR EXTENSIONS AT TOP
 AND BOTTOM.
  
 OPEN SIDED STAIRS REQUIRE 42" HIGH
 HAND/GUARD RAILS.SEE SBC 1015.1.
  
 PROVIDE SPECIFIC CONNECTION DETAILS.
 TERMS SUCH AS "FULL FILLET WELD" ARE
 INADEQUATE.SEE SBC 2207.
  
 PROVIDE CALCULATIONS DEMONSTRATING
 COMPLIANCE WITH SBC 1604.1 AND 1608.2.
  
 WHAT IS 2" X #9 EXPANDED METAL?