| Plan Review Notes For Permit 01061304 |
| Permit Number |
01061304 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-09 00:00:00 | DENIED; | | | | | | 1.SHOW SIZE, TYPE AND LOCATION OF | | | BACKFLOW PROTECTION 94 SPC SEC. 606. | | | | | | 2.SHOW DRAINS FOR EYEWASH AND DRENCH | | | SHOWERS. | | | | | | 3.SHOW CALKULATIONS FOR OIL INTERCEPTER | | | IS INTERCEPTER LARGE ENOUGH TO EXCEPT | | | THE ADDITIONAL FLOW? | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|