Plan Review Notes
Plan Review Notes For Permit 01061304
Permit Number 01061304
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-07-02 00:00:00FAILED :
 1. PLEASE PROVIDE STORM WATER
 CALCULATIONS DUE TO THE CHANGES FOR OUR
 REVIEW.
 2. PLEASE PROVIDE PERVIOUS & IMPERVIOUS
 CALCULATIONS FOR ENTIRE SITE, DUE TO THE
 CHANGES.
 3. PLEASE INCLUDE PLANS, NOTES, DETAILS
 TO DIRECT THE CONTRACTOR TO PROTACT THE
 EXISTING CATCH BASINS AND STORM WATER
 SYS. DURING THE CONSTRUCTION.
 4. AN APPROVED BACKFLOW PREVENTER ASS.
 WILL NEED TO BE INSTALLED, IF NOT
 ALREADY IN PLACE AT THE POINT OF SERVICE
 ON PRIVATE PROPERTY.
 5. A CLEAN-OUT WILL NEED TO BE INSTALLED
 IN SANITARY SEWER LATERAL, ON THE
 PROPERTY IF NOT ALREADY INSTALLED.
 6. THE CITY'S STANDARD DETAILS MAY BE
 OBTAIN THROUGH PUBLIC UTILITIES
 ENGINEERING SERVICES. 659-8040
  
 IF ANY QUESTION PLEASE CONTACT 659- 8096
 EXT. 8492