| Plan Review Notes For Permit 01061304 |
| Permit Number |
01061304 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-02 00:00:00 | FAILED : | | | 1. PLEASE PROVIDE STORM WATER | | | CALCULATIONS DUE TO THE CHANGES FOR OUR | | | REVIEW. | | | 2. PLEASE PROVIDE PERVIOUS & IMPERVIOUS | | | CALCULATIONS FOR ENTIRE SITE, DUE TO THE | | | CHANGES. | | | 3. PLEASE INCLUDE PLANS, NOTES, DETAILS | | | TO DIRECT THE CONTRACTOR TO PROTACT THE | | | EXISTING CATCH BASINS AND STORM WATER | | | SYS. DURING THE CONSTRUCTION. | | | 4. AN APPROVED BACKFLOW PREVENTER ASS. | | | WILL NEED TO BE INSTALLED, IF NOT | | | ALREADY IN PLACE AT THE POINT OF SERVICE | | | ON PRIVATE PROPERTY. | | | 5. A CLEAN-OUT WILL NEED TO BE INSTALLED | | | IN SANITARY SEWER LATERAL, ON THE | | | PROPERTY IF NOT ALREADY INSTALLED. | | | 6. THE CITY'S STANDARD DETAILS MAY BE | | | OBTAIN THROUGH PUBLIC UTILITIES | | | ENGINEERING SERVICES. 659-8040 | | | | | | IF ANY QUESTION PLEASE CONTACT 659- 8096 | | | EXT. 8492 |
|