| Plan Review Notes For Permit 01061290 |
| Permit Number |
01061290 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-17 00:00:00 | ****************** UNSAT *************** | | | | | | | | | 1)NOTE: PLEASE NOTE THAT PER FS AND FAC | | | 471.025 AND 481.221 PLANS DONE BY AN | | | ARCH/AND OR ENGINEER NEED TO BE SIGNED, | | | DATED AND SEALED BY THAT PERSON OF | | | RECORD. | | | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 3)NOTE: PLEASE NOTE THAT ALL OUTSIDE | | | OUTLETS ARE TO BE SHOWN AS GFI 210-8. | | | | | | 4)NOTE: PLEASE CALRIFY PANEL SHOWN AS | | | "MCB" WHEN A MAIN IS SHOWN FOR OUTSIDE | | | WITH METER.?? | | | | | | 5)NOTE: PLEASENOTE THAT PLANS SHOW | | | TWO A/C COND UNITS AND PANEL/LOAD CALCS | | | ONLY SHOW ONE? PLEASE CLARIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|