2001-07-17 00:00:00****************** UNSAT ***************
  
  
 1)NOTE: PLEASE NOTE THAT PER FS AND FAC
 471.025 AND 481.221 PLANS DONE BY AN
 ARCH/AND OR ENGINEER NEED TO BE SIGNED,
 DATED AND SEALED BY THAT PERSON OF
 RECORD.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3)NOTE: PLEASE NOTE THAT ALL OUTSIDE
 OUTLETS ARE TO BE SHOWN AS GFI 210-8.
  
 4)NOTE: PLEASE CALRIFY PANEL SHOWN AS
 "MCB" WHEN A MAIN IS SHOWN FOR OUTSIDE
 WITH METER.??
  
 5)NOTE: PLEASENOTE THAT PLANS SHOW
 TWO A/C COND UNITS AND PANEL/LOAD CALCS
 ONLY SHOW ONE? PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  