| Plan Review Notes For Permit 01061260 |
| Permit Number |
01061260 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-08-29 00:00:00 | *************BUILDING UNSAT************* | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) THE ADDITION DOES NOT COMPLY WITH | | | TABLE 600 OF THE 97 SBC. THE PERCENT OF | | | WALL OPENINGS ALLOWED IS EXCEEDED ON THE | | | WEST SIDE OF THE ADDITION. (33.2 SQFT OF | | | OPENINGS IS ALLOWED.) | | | | | | 4) PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - STRUCTURAL WINDOW MULLIONS | | | | | | 5) PROVIDE INSTALLATION SCHEDULE AND | | | INDICATE THE SPECIFIC TYPE ANCHOR TO BE | | | USED FOR STORM PANELS. | | | | | | TRUSSES | | | UNSAT | | | | | | 1) THE TRUSS LAYOUT MUST BE REVIEWED | | | AND APPROVED BY THE DESIGNER OF RECORD. | | | (CONSULTING ENGINEER) | | | | | | 2) EACH OF THE TRUSS DRAWINGS MUST HAVE | | | THE WET SIGNATURE OF THE TRUSS ENGINEER | | | IN ADDITION TO HIS SEAL AND THE DATE | | | THAT THE SIGNATURE AND SEAL IS AFFIXED | | | IMMEDIATELY UNDER THE SIGNATURE PER FAC | | | 61G15-23.002. |
|