| 2001-08-07 00:00:00 | ************** UNSAT ******************* |
| | |
| | 1)NOTE: PLEASE NOTE THAT PERMIT |
| | APPLICATION DOES NOT CORRELATE WITH |
| | PLANS SUBMITTED FOR REVIEW. PERMIT APP |
| | SAY NEW FLA |
| | ROOM AND SECOND FLOOR ADDITION ON HOUSE. |
| | YET PLANS SHOW COTTAGE. WHICH ONE? |
| | |
| | |
| | 2)NOTE: PLEASE NOTE PLANS SHOW NEW |
| | SERVICE BEING INSTALLED. PLEASE CLARFIY |
| | HOW |
| | MAIN HOUSE IS BEING FED? |
| | GROUNDING ELECTRODE SYSTEM PER 250-50 |
| | WIRE SIZES, |
| | CONDUIT SIZES, |
| | AIC RATINGS, |
| | ETC |
| | |
| | NOT ENOUGH ELECTRICAL DETAIL WAS |
| | SUBMITTED FOR FULL REVIEW OF PLANS. |
| | PLEASE ALSO HAVE PLANS REDRAWN FOR |
| | ELECTRICAL, THERE ARE WAY TOO MANY |
| | HANDWRITTEN CHANGES FOR FIRST TIME IN. |
| | PER COUNTY-WIDE AND CITY-WIDE |
| | ADMINISTRATIVE CODE.104.2 |
| | |
| | |
| | 4)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 5) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 6) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |