| Plan Review Notes For Permit 01061258 |
| Permit Number |
01061258 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-08-07 00:00:00 | SBC 412.6.1 REQUIRES ELEVATOR LOBBIES TO | | | BE SEPARATED FROM THE REMAINDER OF THE | | | BUILDING WITH ONE HOUR CONSTRUCTION AND | | | TWENTY MINUTE RATED OPENING PROTECTIVES. | | | A "WATER CURTAIN" IN AND OF ITSELF IS | | | NOT A LISTED ASSEMBLY OR A SUBSTITUTE | | | FOR ONE. | | | | | | SEE SBC 705.1.3 FOR OPENING PROTECTION | | | REQUIREMENTS. | | | | | | SEE SBC TABLE 705.1.2 FOR ELEVATOR SHAFT | | | DOOR RATINGS. |
|