2001-08-07 00:00:00SBC 412.6.1 REQUIRES ELEVATOR LOBBIES TO
 BE SEPARATED FROM THE REMAINDER OF THE
 BUILDING WITH ONE HOUR CONSTRUCTION AND
 TWENTY MINUTE RATED OPENING PROTECTIVES.
 A "WATER CURTAIN" IN AND OF ITSELF IS
 NOT A LISTED ASSEMBLY OR A SUBSTITUTE
 FOR ONE.
  
 SEE SBC 705.1.3 FOR OPENING PROTECTION
 REQUIREMENTS.
  
 SEE SBC TABLE 705.1.2 FOR ELEVATOR SHAFT
 DOOR RATINGS.