| Plan Review Notes For Permit 01061258 |
| Permit Number |
01061258 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-27 00:00:00 | 1) PLEASE PROVIDE OCCUPANT LOAD | | | CALCULATIONS FOR TENANT SPACE. | | | 2) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | 3) PLEASE PROVIDE MORE DETAILS ON DOORS | | | WHERE "WATER CURTAIN" IS PLANNED. IS THE | | | GLASS TEMPERED, SAFETY OR HAVE A FIRE | | | RATING. | | | 4) PLEASE PROVIDE MORE INFORMATION ON | | | SECURITY FEATURES PLANNED FOR EXIT | | | DOORS. DO THE SECURITY FEATURES THAT ARE | | | PLANNED MEET THE REQUIREMENTS OF SPECIAL | | | LOCKING ARRANGEMENTS IN THE LIFE SAFETY | | | CODE, 1985 EDITION. ARE THESE DOORS | | | FAIL SAFE OR FAIL SECURE IN THE EVENT OF | | | A PROBLEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|