| Plan Review Notes For Permit 01061258 |
| Permit Number |
01061258 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-10 00:00:00 | PROVIDE THE TEST REPORT FOR THE WATER | | | CURTAIN AT THE GLASS DOOR. | | | | | | NOTE 11 ON G2 RE PLANTONS FOR DOORS | | | MUST COMPLY WITH NFPA 80 | | | | | | NOTE 22, G2 RE UNDERCUT OF DOORS MUST | | | COMPLY WITH NFPA 80 FOR ANY FIRE RATED | | | DOORS. | | | | | | A LIFE SAFETY PLAN MUST ACCOMPANY THE | | | PERMIT FOR THE TEMPORARY DEMISING OF | | | THEFLOOR PLAN SHOWN ON SHEET D1.TWO | | | INDEPENDENT MEANS OF EGRESS MUST BE | | | MAINTAINED.SBC 1004.2.2 | | | | | | DOOR #123D AT THE ELEVATOR LOBBY IS | | | REQUIRED TO BE 20 MINUTE FIRE RATED. | | | SEE SBC 412.6.1. | | | | | | PROVIDE THE HC ACCESSIBILTY TO THE | | | TOILET ROOMS AND DRINKING FOUNTAINS AS | | | REQUIRED BY FCBC 4.1.6. (2) (A)(III) | | | AND (V) |
|