2001-09-21 00:00:00CHECKLIST:
 1-NEED TO RECORD NOTICE OF COMMENCEMENT.
 2-UTILITY ROOM STAIRS NEED A LANDING.
 SEC. 1012.1.6 SBC 1997.
 3-SPECIFY SAFETY GLASS AT BEDROOM #2.
 SEE PLANS. SEC. 2405.2 SBC 1997.
 4-CLARIFY WHICH ONE IS THE EGRESS WINDOW
 FROM BEDROOM #2 THAT COMPLY WITH SEC.
 1005.4 SBC 1997. IF IT IS THE ONE AT
 LEFT SIDE OF ROOM, THEN, WHY IS THERE
 A MULLION SHOWN IN THE MIDDLE?.
 PROVIDE SIZES OF WINDOWS TO VERIFY
 CLEAR DIMENSIONS.
 5-SPECIFY SIZE OF ATTIC VENTS TO VERIFY
 COMPLIANCE WITH SEC. 2309.7 SBC 1997.
 6-TRUSS CONNECTOR SPECIFIED LSTA IS A
 WOOD TO WOOD CONNECTOR, NOT A WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
 SPECIFY CONNECTOR THAT WILL RESIST THE
 LATERAL LOADS AS WELL.
 7-PROVIDE COMPLETE CONSTRUCTION DETAILS
 FOR BAY WINDOW. SPECIFY SIZE AND TYPE
 OF COLUMNS. FASTENERS OF COLUMNS: TOP
 AND BOTTOM. SPECIFY CONNECTORS FOR
 WOOD LINTELS AT THE ENDS AND TO THE
 COLUMNS.
 8-OWES $203.07 FOR UPDATED CONSTRUCTION
 VALUE AND RADON FEES. PAY ATTACHED
 RECEIPT AND BRING PAID RECEIPT.
  
  
 NOTES:
 A-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS AT TIME OF RESUBMITTAL OR APPLY
 FOR SEPARATE PERMIT.
 B-PROVIDE MISSING PRODUCT APPROVALS AT
 TIME OF RESUBMITTAL OR BEFORE INSTALL-
 ATION IF TIME IS NEED IT.