| Date |
Text |
| 2001-09-21 00:00:00 | CHECKLIST: |
| | 1-NEED TO RECORD NOTICE OF COMMENCEMENT. |
| | 2-UTILITY ROOM STAIRS NEED A LANDING. |
| | SEC. 1012.1.6 SBC 1997. |
| | 3-SPECIFY SAFETY GLASS AT BEDROOM #2. |
| | SEE PLANS. SEC. 2405.2 SBC 1997. |
| | 4-CLARIFY WHICH ONE IS THE EGRESS WINDOW |
| | FROM BEDROOM #2 THAT COMPLY WITH SEC. |
| | 1005.4 SBC 1997. IF IT IS THE ONE AT |
| | LEFT SIDE OF ROOM, THEN, WHY IS THERE |
| | A MULLION SHOWN IN THE MIDDLE?. |
| | PROVIDE SIZES OF WINDOWS TO VERIFY |
| | CLEAR DIMENSIONS. |
| | 5-SPECIFY SIZE OF ATTIC VENTS TO VERIFY |
| | COMPLIANCE WITH SEC. 2309.7 SBC 1997. |
| | 6-TRUSS CONNECTOR SPECIFIED LSTA IS A |
| | WOOD TO WOOD CONNECTOR, NOT A WOOD TO |
| | MASONRY CONNECTOR. REVISE AS REQUIRED. |
| | SPECIFY CONNECTOR THAT WILL RESIST THE |
| | LATERAL LOADS AS WELL. |
| | 7-PROVIDE COMPLETE CONSTRUCTION DETAILS |
| | FOR BAY WINDOW. SPECIFY SIZE AND TYPE |
| | OF COLUMNS. FASTENERS OF COLUMNS: TOP |
| | AND BOTTOM. SPECIFY CONNECTORS FOR |
| | WOOD LINTELS AT THE ENDS AND TO THE |
| | COLUMNS. |
| | 8-OWES $203.07 FOR UPDATED CONSTRUCTION |
| | VALUE AND RADON FEES. PAY ATTACHED |
| | RECEIPT AND BRING PAID RECEIPT. |
| | |
| | |
| | NOTES: |
| | A-PROVIDE COMPLETE INFORMATION FOR STORM |
| | PANELS AT TIME OF RESUBMITTAL OR APPLY |
| | FOR SEPARATE PERMIT. |
| | B-PROVIDE MISSING PRODUCT APPROVALS AT |
| | TIME OF RESUBMITTAL OR BEFORE INSTALL- |
| | ATION IF TIME IS NEED IT. |