| Plan Review Notes For Permit 01061214 |
| Permit Number |
01061214 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-19 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT A COMPLETE NEW | | | RISER DIGRAM IS NOW BEING SUBMITTED FOR | | | REVIEW. | | | PLEASE NOTE THAT PLANS SHOW A MAIN DISC- | | | -ONNECT IN FRONT OF FPL`S METERING?? | | | THIS IS NOT PERMITTED.PER FPL. | | | PLEASE ALSO NOTE THAT PER ZONING, ONLY | | | ONE METER CAN BE INSTALLED FOR RESIDENCE | | | A GUEST HOUSE IS PERMITTED BUT NOT A | | | SECOND METER, IN SF-14 AREA.(SINGLE FAM) | | | | | | | | | 2)NOTE: PLEASE ALSO NOTE THAT NOT ALL | | | NOTES FROM FIRST REVIEW WERE ADDRESSED. | | | | | | 3)NOTEL PLEASE NOTE MISSING OUTLETS FOR | | | KITCHEN COUNTER-SPACE PER 210-52-C-1,2,3 | | | ,4,5. | | | | | | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 5)NOTE:PLEASE NOTE THAT NEW SERVICE CAN | | | BE LOCATED ON "FUTURE" GUEST HOUSE BUT, | | | PLANS SHOW NEW HOUSE PANEL HAVING NO | | | MAIN?? PER 225-31. | | | | | | 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IFTHERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | 2001-09-18 00:00:00 | ****************** UNSAT ************* |
|