Plan Review Notes For Permit 01061214
Permit Number 01061214
Review Stop E
Sequence Number 2
Notes
Date Text
2001-09-19 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT A COMPLETE NEW
 RISER DIGRAM IS NOW BEING SUBMITTED FOR
 REVIEW.
 PLEASE NOTE THAT PLANS SHOW A MAIN DISC-
 -ONNECT IN FRONT OF FPL`S METERING??
 THIS IS NOT PERMITTED.PER FPL.
 PLEASE ALSO NOTE THAT PER ZONING, ONLY
 ONE METER CAN BE INSTALLED FOR RESIDENCE
 A GUEST HOUSE IS PERMITTED BUT NOT A
 SECOND METER, IN SF-14 AREA.(SINGLE FAM)
  
  
 2)NOTE: PLEASE ALSO NOTE THAT NOT ALL
 NOTES FROM FIRST REVIEW WERE ADDRESSED.
  
 3)NOTEL PLEASE NOTE MISSING OUTLETS FOR
 KITCHEN COUNTER-SPACE PER 210-52-C-1,2,3
 ,4,5.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5)NOTE:PLEASE NOTE THAT NEW SERVICE CAN
 BE LOCATED ON "FUTURE" GUEST HOUSE BUT,
 PLANS SHOW NEW HOUSE PANEL HAVING NO
 MAIN?? PER 225-31.
  
 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IFTHERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372