| 2001-07-17 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | |
| | 3) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 4) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | MISSING DOWNSTAIRS. |
| | |
| | 5) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. AT DETACHED BLDG. |
| | |
| | 6) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. |
| | |
| | 7)NOTE: PLEASE NOTE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR BETWEENHOUSE AND |
| | OTHER STRUCTURE. SIZE 250-122 |
| | |
| | 8)NOTE: PLEASE NOTE THAT PANEL AT NEW HO |
| | USE SHOWS MLO? PLEASE CLARIFY MEANS OF |
| | DISCONNECT FOR STRUCTURE PER 225-31&32 |
| | |
| | |
| | 9)NOTE: PLEASE NOTE THAT FEEDERS TO |
| | MAIN HOUSE SHOW 2# 0?? PLEASE CALRIFY |
| | WIRE SIZE. 0 DOES NOT CORRELATE TO ANY |
| | AWG. |
| | |
| | 10)NOTE: PLEASE NOTE THAT PANEL SCHEDULE |
| | FOR EXISTING HOUSE DOES NOT SHOW BREAKER |
| | SIZE FEEDING NEW HOUSE. PLEASE CLARIFY |
| | 150A ?? FEED TO HOUSE. PLEASE NOTE THAT |
| | EXSITING PANEL WILL MOST LIKELY NOT BE |
| | ABLE TO HOLD A 150A 2-P BRKR>?? |
| | PLEASE CLARIFY. |
| | |
| | 11)NOTE: PLEASE NOTE THAT PLANS SAY TO |
| | VERIFY SERVICE ENTRANCE CONDUCTORS? |
| | PLEASE NOTE THAT WE NEED TO KNOW WHAT |
| | SIZE EXSITING CONDUCTORS ARE. 215-5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW, IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |