| Plan Review Notes For Permit 01061187 |
| Permit Number |
01061187 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-05 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASE CLARIFY MEANS OF EQUIP- | | | -MENT GROUNDING BETWEEN DISCONNECT AND | | | PANEL AND PANEL AND PANEL "H". | | | GROUNDING OF TRANSFORMER. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE AREANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|