| Plan Review Notes For Permit 01061173 |
| Permit Number |
01061173 |
|
| Review Stop |
R |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2002-10-10 00:00:00 | SUBMITTAL DENIED | | | | | | BUTT GLAZING | | | | | | 1) THE ENGINEERING FOR THE BUTT GLAZING | | | MUST BE REVIEWED AND APPROVED BY THE | | | DESIGNER OF RECORD FOR THE STRUCTURE. | | | | | | 2) THE WIND PRESSURE AT THIS OPENING IS | | | GIVEN AS -48 AND +47 PSF ON SHEET A-5 OF | | | THE PLANS. THE PRODUCT ENGINEERING IS | | | ONLY GOOD FOR -34.2 AND +33.6 PSF. | | | | | | | | | FRONT DOORS | | | | | | 1) THE PRODUCT APPROVAL SUBMITTAL FORM | | | IS ILLEGIBLE. | | | | | | 2) THE ENGINEER'S SIGNATURE IS NOT | | | ORIGINAL. | | | | | | 3) THE ENGINEER'S NAME AND LICENSE | | | NUMBER SHOULD BE ON DOCUMENT AND BE | | | LEGIBLE. | | | | | | 4) INSTALLATION SITE LOCATION IS | | | REQUIRED TO BE ON THE FORM. | | | | | | 5) THE DESIGNER OF RECORD IS REQUIRED TO | | | REVIEW AND APPROVE THE INFORMATION AND | | | SIGN AND SEAL THE FORM. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|