2002-10-10 00:00:00SUBMITTAL DENIED
  
 BUTT GLAZING
  
 1) THE ENGINEERING FOR THE BUTT GLAZING
 MUST BE REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD FOR THE STRUCTURE.
  
 2) THE WIND PRESSURE AT THIS OPENING IS
 GIVEN AS -48 AND +47 PSF ON SHEET A-5 OF
 THE PLANS. THE PRODUCT ENGINEERING IS
 ONLY GOOD FOR -34.2 AND +33.6 PSF.
  
  
 FRONT DOORS
  
 1) THE PRODUCT APPROVAL SUBMITTAL FORM
 IS ILLEGIBLE.
  
 2) THE ENGINEER'S SIGNATURE IS NOT
 ORIGINAL.
  
 3) THE ENGINEER'S NAME AND LICENSE
 NUMBER SHOULD BE ON DOCUMENT AND BE
 LEGIBLE.
  
 4) INSTALLATION SITE LOCATION IS
 REQUIRED TO BE ON THE FORM.
  
 5) THE DESIGNER OF RECORD IS REQUIRED TO
 REVIEW AND APPROVE THE INFORMATION AND
 SIGN AND SEAL THE FORM.
  