| 2001-07-27 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) PROVIDE EGRESS WINDOW IN EXERCISE |
| | ROOM, WHICH COULD BE USED AS A SLEEPING |
| | ROOM. 97 SBC 1005.4 |
| | |
| | 3) PROVIDE ENGINEERING FOR BUTT GLASS |
| | ASSEMBLIES PER 1997 SBC 2406.2. |
| | |
| | 4) PROVIDE AT LEAST ONE BATHROOM WITH A |
| | DOOR THAT HAS A 29" CLEAR OPENING PER 97 |
| | FLORIDA ACCESSIBILITY CODE 4.22.2. |
| | |
| | 5) PROVIDE ROOF FRAMING PLAN FOR CHIMNEY |
| | INDICATING CONNECTORS THAT WILL BE USED |
| | TO ANCHOR TRUSSES. |
| | |
| | 6) THE NAIL SPACING FOR ROOFS USING 8D |
| | COMMON NAILS IN ZONE 3 IS 4" AT THE |
| | EDGES AND 6" INTERMEDIATE PER CITY |
| | AMENDMENTS TO THE 97 SBC SEC.2306. |
| | PLEASE CORRECT SCHEDULE ON SHEET A-8. |
| | |
| | 7) PLEASE CLARIFY DETAIL AA-2 AND AA-3 |
| | INDICATED ON SHEET A-7. THEY ARE NOT |
| | SHOWN ON SHEET A-8. |
| | |
| | 8) SPECIFY THE CONNECTORS FOR ALL OF THE |
| | TRUSSES NOT SPECIFICALLY INDICATED ON |
| | SHEET A-7. |
| | |
| | 9)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - STRUCTURAL MULLIONS FOR WINDOW |
| | ASSEMBLIES |
| | - STRUCTURAL MULLIONS FOR DOOR WITH |
| | TRANSOM ABOVE ASSEMBLIES |
| | - CASEMENT WINDOWS |
| | |
| | NOTE: ALL EXTERIOR GLAZINGS TO BE IMPACT |
| | GLASS OR STORM PANELS WILL BE REQUIRED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |