| Plan Review Notes For Permit 01061165 |
| Permit Number |
01061165 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-28 00:00:00 | *******************PROVISO************** | | | | | | | | | THE FOLLOWING NOTES WERE NEVER ADDRESSED | | | ON PLAN REVIEW WITH MASTER PERMIT | | | #00071404. | | | | | | PLEASE PROVIDE ENERGY EFFICIENCY RATING | | | OF SYSTEM AS PER FLORIDA ENERGY EFFIENCY | | | CODE. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH | | | NOTIFICATION BY FIRE ALARM SYSTEM OR | | | TIED IN TO HORM/STROBE AS PER NFPA 90A | | | 4-4.4.2 OF 4-4.4.3. | | | | | | SEPERATE PLANS AND PERMIT FOR FIRE | | | SUPRESSION SYSTEM. | | | | | | NOTE:EQUIPMENT ON ROOF SHALL COMPLY | | | WITH AMENDED 1997 SMC 304.2.5, | | | 18" MINIMUM BETWEEN ROOF SURFACE | | | AND BOTTOM OF SUPPORT RAIL. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|