| 2001-09-26 00:00:00 | PLUMBING FOUNDATION PLAN REVIEW,PROVISO | | | (1) SHT P2-1.3 TRASH COMPACTOR TRENCH | | | DRAIN TO GREASE WASTE. | | | (2)SHT P2-1.7, 3" VENT ON CONDENSATE NOT | | | APPROVED, PROVIDE A 3" RELIEF VENT OUT | | | SIDE, TERMINATE 6" ABOVE GRADE WITH A | | | 180 DEGREE ELBOW. | | | WHEN THE BUILDING IS SUBJECT TO BACK | | | WATER (CONDENSATE) A BACK WATER VALVE | | | IS REQUIRED,SPC-94 SEC 1101.5 | | | (3) SHT P2-4.2 OVER-FLO-DAINS TIED | | | TOGETHER,ARCHITURAL PLANS SHOW | | | INDIVIDUAL DRAINS? | | | (4) SHT P2-1.8 RWL COL 20 & W, TICKET | | | OFFICE AREA, 4" RWL TIED IN TWICE, ALSO | | | 1" CONDENSATE TO BE RUN SEPERATE. | | | (5) SHT P2-1.7 RM #1E22 TRASH HOLDING | | | AREA, WHAT TYPE OF TRASH IS STORED HERE? | | | IF THIS IS RESTAURANT WASTE, THIS F/D | | | WILL NEED TO GO TO GREASE WASTE. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561 659-8096X8233 |
|