Plan Review Notes
Plan Review Notes For Permit 01061114
Permit Number 01061114
Review Stop P
Sequence Number 2
Notes
Date Text
2001-09-26 00:00:00PLUMBING FOUNDATION PLAN REVIEW,PROVISO
 (1) SHT P2-1.3 TRASH COMPACTOR TRENCH
 DRAIN TO GREASE WASTE.
 (2)SHT P2-1.7, 3" VENT ON CONDENSATE NOT
 APPROVED, PROVIDE A 3" RELIEF VENT OUT
 SIDE, TERMINATE 6" ABOVE GRADE WITH A
 180 DEGREE ELBOW.
 WHEN THE BUILDING IS SUBJECT TO BACK
 WATER (CONDENSATE) A BACK WATER VALVE
 IS REQUIRED,SPC-94 SEC 1101.5
 (3) SHT P2-4.2 OVER-FLO-DAINS TIED
 TOGETHER,ARCHITURAL PLANS SHOW
 INDIVIDUAL DRAINS?
 (4) SHT P2-1.8 RWL COL 20 & W, TICKET
 OFFICE AREA, 4" RWL TIED IN TWICE, ALSO
 1" CONDENSATE TO BE RUN SEPERATE.
 (5) SHT P2-1.7 RM #1E22 TRASH HOLDING
 AREA, WHAT TYPE OF TRASH IS STORED HERE?
 IF THIS IS RESTAURANT WASTE, THIS F/D
 WILL NEED TO GO TO GREASE WASTE.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561 659-8096X8233