Plan Review Notes
Plan Review Notes For Permit 01061114
Permit Number 01061114
Review Stop P
Sequence Number 1
Notes
Date Text
2001-07-21 00:00:00PLUMBING PLAN REVIEW,FOUNDATION ONLY
 CODE REFERENCES,STD PLBG-94,STD GAS-97,
 FL ACCESSIBILTY CODE FOR BLDG CONST-97
 BUILDINGPLAN REVIEW TO FOLLOW
 "PROVISO"
 ALL WORK PER CITY CODES,SUBJECT TO FIELD
 INSPECTOR APPROVAL.
 (1) DEPT OF HOTEL BUSINESS REGULATION
 PLAN REVIEW AND COMMENTS BEFORE PLUMBING
 PLAN REVIEW APPROVAL, 954-958-5520.
 (2) GREASE TRAP TO BE SIZED BY W. PALM
 BCH RSTP, ENVIROMENTAL COMPLIANCE.
 CONTACT, RODNEY COMPO 561-837-4074.
 LOCAL ORD# 2938-96. SEPERATE PERMIT REQ.
 (3) MODEL CNTY WIDE AMENDMENTS TO SPC-94
 SEC 804.3 A/C CONDENSATE, PROVIDE COMMON
 SYSTEM FOR ENTIRE BLDG, CONNECTED TO THE
 STORM DRAINAGE,OUT SIDE OF THE BUILDING,
 WITH A RELIEF VENT.
 (4) MINIMUM FACILITIES SEC 407.1.3 SHOW
 CALCULATIONS FOR NUMBER OF PERSONS FOR
 THE ENTIRE BLDG,BROKEN DOWN TO THE REST
 RM'S IN EACH AREA, FOR PLAN REVIEW APPR.
 (5) PUBLIC REST RM'S TO COMPLY W/FACBC97
 TOILET STALLS, SIZE AND ARRANGMENT, DCA
 RULE 9B-7.0042, FL ADM CODE ,FIG 30(E).
 SIX OR MORE W/C,SEC 4.23.4-ONE ADDITONAL
 STALL.SIZE & DOOR SWING, SEC 4.17.3.
 URINAL SEC 4.18 HEIGHT,CLEAR FLR SPACE.
 (6) SEC 409.4 FLR DRAINS IN PUBLIC REST
 RM'S, TRAP PRIMERS REQ.
 (7) SEC 104.3 PLANS,SANITARY SEWER.SHOW
 FIXTURE LOAD ON ENTIRE SYSTEM,INCLUDING
 BRANCHES. PRIOR TO INSTALLATION.
 (8)ELEVATOR SUMP PITS,QUESTION ON DRAIN.
 (9) SHT P2-1.3 COL C-C8,13-14, CAN WASH,
 TO GREASE WASTE, LOCAL ORD# 2938-96
 (10) DISH WASHERS, TO SANITARY SEWER,
 LOCAL ORD# 2938-96.
 (11) ALL INDIRECT WASTE TO FLR SINKS,
 NO HUB DRAINS.SEC SEC 802.
 (12) SHTS P2-1.2 TO P2-1.8 EXHIBIT AREA
 DRAINS. COMPLY W/SEC 921,"HORIZONTAL"
 COMBINATION WASTE AND VENT SYSTEM, SEE
 PG-275,276 ILLUSTRATIONS, NO DRY VENTS.
 (13)SHT P2-1.1 REST RM,IN-23,24.TYPICAL.
 SEC 914, CIRUIT & LOOP VENTS, FIXTURES
 FROM UPPER FLRS SHALL NOT DISCHARGE INTO
 A BATTERY VENTED BRANCH.
 (14) SHT P2-1.1 TO P2-1.8 EXHIBIT AREA,
 PROVIDE MFG. CUT SHEET ON UTILITY BOX,
 PRIOR TO INSTALLATION, FOR APPROVAL.
 (15) SHT P2-1.1 TO P2-2.8, U/G PRIMARY
 STORM DRAINAGE SYSTEM, SEC 1108.2.2
 PROVIDE CALCULATIONS FOR DRAINAGE SYSTEM
 ,INCLUDE CALCULATIONS FOR VERTICAL WALLS
 SEC 1108.3
 END OF COMMENTSPAUL SCHMITZ