| 2001-07-21 00:00:00 | PLUMBING PLAN REVIEW,FOUNDATION ONLY |
| | CODE REFERENCES,STD PLBG-94,STD GAS-97, |
| | FL ACCESSIBILTY CODE FOR BLDG CONST-97 |
| | BUILDINGPLAN REVIEW TO FOLLOW |
| | "PROVISO" |
| | ALL WORK PER CITY CODES,SUBJECT TO FIELD |
| | INSPECTOR APPROVAL. |
| | (1) DEPT OF HOTEL BUSINESS REGULATION |
| | PLAN REVIEW AND COMMENTS BEFORE PLUMBING |
| | PLAN REVIEW APPROVAL, 954-958-5520. |
| | (2) GREASE TRAP TO BE SIZED BY W. PALM |
| | BCH RSTP, ENVIROMENTAL COMPLIANCE. |
| | CONTACT, RODNEY COMPO 561-837-4074. |
| | LOCAL ORD# 2938-96. SEPERATE PERMIT REQ. |
| | (3) MODEL CNTY WIDE AMENDMENTS TO SPC-94 |
| | SEC 804.3 A/C CONDENSATE, PROVIDE COMMON |
| | SYSTEM FOR ENTIRE BLDG, CONNECTED TO THE |
| | STORM DRAINAGE,OUT SIDE OF THE BUILDING, |
| | WITH A RELIEF VENT. |
| | (4) MINIMUM FACILITIES SEC 407.1.3 SHOW |
| | CALCULATIONS FOR NUMBER OF PERSONS FOR |
| | THE ENTIRE BLDG,BROKEN DOWN TO THE REST |
| | RM'S IN EACH AREA, FOR PLAN REVIEW APPR. |
| | (5) PUBLIC REST RM'S TO COMPLY W/FACBC97 |
| | TOILET STALLS, SIZE AND ARRANGMENT, DCA |
| | RULE 9B-7.0042, FL ADM CODE ,FIG 30(E). |
| | SIX OR MORE W/C,SEC 4.23.4-ONE ADDITONAL |
| | STALL.SIZE & DOOR SWING, SEC 4.17.3. |
| | URINAL SEC 4.18 HEIGHT,CLEAR FLR SPACE. |
| | (6) SEC 409.4 FLR DRAINS IN PUBLIC REST |
| | RM'S, TRAP PRIMERS REQ. |
| | (7) SEC 104.3 PLANS,SANITARY SEWER.SHOW |
| | FIXTURE LOAD ON ENTIRE SYSTEM,INCLUDING |
| | BRANCHES. PRIOR TO INSTALLATION. |
| | (8)ELEVATOR SUMP PITS,QUESTION ON DRAIN. |
| | (9) SHT P2-1.3 COL C-C8,13-14, CAN WASH, |
| | TO GREASE WASTE, LOCAL ORD# 2938-96 |
| | (10) DISH WASHERS, TO SANITARY SEWER, |
| | LOCAL ORD# 2938-96. |
| | (11) ALL INDIRECT WASTE TO FLR SINKS, |
| | NO HUB DRAINS.SEC SEC 802. |
| | (12) SHTS P2-1.2 TO P2-1.8 EXHIBIT AREA |
| | DRAINS. COMPLY W/SEC 921,"HORIZONTAL" |
| | COMBINATION WASTE AND VENT SYSTEM, SEE |
| | PG-275,276 ILLUSTRATIONS, NO DRY VENTS. |
| | (13)SHT P2-1.1 REST RM,IN-23,24.TYPICAL. |
| | SEC 914, CIRUIT & LOOP VENTS, FIXTURES |
| | FROM UPPER FLRS SHALL NOT DISCHARGE INTO |
| | A BATTERY VENTED BRANCH. |
| | (14) SHT P2-1.1 TO P2-1.8 EXHIBIT AREA, |
| | PROVIDE MFG. CUT SHEET ON UTILITY BOX, |
| | PRIOR TO INSTALLATION, FOR APPROVAL. |
| | (15) SHT P2-1.1 TO P2-2.8, U/G PRIMARY |
| | STORM DRAINAGE SYSTEM, SEC 1108.2.2 |
| | PROVIDE CALCULATIONS FOR DRAINAGE SYSTEM |
| | ,INCLUDE CALCULATIONS FOR VERTICAL WALLS |
| | SEC 1108.3 |
| | END OF COMMENTSPAUL SCHMITZ |