1 |
|
| Notes |
| Date |
Text |
| 2001-07-18 00:00:00 | FOUNDATION PERMIT REVIEW COMMENTS. | | | 1. PAY IMPACT FEES. | | | 2. SPECIAL INSPECTOR PLAN, SUBMIT FOR | | | REVIEW AND APPROVAL. | | | 3. PERMIT DOES NOT INCLUDE ANY WORK | | | ABOVE THE SLAB. | | | 4. PROVIDE EASEMENT INFORMAION FOR ALL | | | ENCROACHMENTS, IE: BELL SOUTH DUCT BANK | | | SEE S3-1.1. | | | 5. SOIL TEST REPORTS SUBMIT. | | | 6. SHEET S4-1.1 QUESTION WHY IS FLOOR | | | LOAD REDUCED IN CLASSROOM AREA FROM 100 | | | PSF TO 40 PSF, NOT REQUIRED FOR | | | FOUNDATION PERMIT. | | | 7. SEE CITY CODE AMENDMENTS SECTION | | | 1804.1.1 ALL FOOTINGS SHALL BE FORMED. | | | 8. SEE CITY CODE AMENDMENTS FOR MASONERY | | | CONSTRUCTION SECTION 2111.6 FOR WATER | | | STOP DETAIL. | | | 9. NOTE SECTION 1 ON S6-1.6 RISE AND | | | RUN OF STAIRS NOT IN COMPLIANCE WITH | | | SBC1007.3.1 AND 1007.3.1B. | | | CONTACT BILL STAPLES AT 561-659-8096 IF | | | ANY QUESTIONS. |
|