| 2001-06-28 00:00:00 | 1) THE FIRE DEPARTMENT CONNECTION SHOWN | | | ON PAGE C-12 FACES THE WRONG DIRECTION. | | | THE CONNECTION SHOULD FACE THE SERVICE | | | ROAD AND NOT THE CMU WALL. | | | 2) A PLATEAU AREA FOR OUTDOOR EXHIBITS | | | IS NOTED ON THE PLANS. WRITER QUESTIONED | | | MIKE ROSSIN AND HE EXPLAINED THAT ONLY | | | TENTS THAT HAVE BEEN PROPERLY PERMITTED | | | AND APPROVED BY THE CITY WILL BE USED | | | IN THIS AREA. | | | 3) FLORIDA AVENUE STILL NEEDS ADDITIONAL | | | FIRE HYDRANTS. | | | 4) THIS REVIEW DOES NOT INCLUDE FIRE | | | HYDRANT LOCATIONS FOR ALABAMA AVENUE, | | | "L" STREET, "N" STREET, ETC. | | | 5) CITY CODE SECTION 11-4, REQUIRES 18 | | | FEET FROM OBSTRUCTIONS TO FIRE HYDRANTS. | | | 6) PLEASE PROVIDE THIS OFFICE A LETTER | | | INDICATING THAT ADDITIONAL FIRE HYDRANTS | | | WILL BE PROVIDED FOR THE CONVENTION | | | CENTER. LOCATION OF THESE HYDRANTS WILL | | | BE DETERMINED IN THE NEAR FUTURE. | | | 7) GAS INSTALLATIONS TO COMPLY WITH | | | NFPA 54. | | | 8) ANY CHANGES IN ELEVATIONS OUTSIDE | | | THE CENTER THAT COMPRISE TWO STEPS MUST | | | HAVE TREADS OF AT LEAST 13" WIDE AND BE | | | VISIBLE TO THE USERS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|