| Plan Review Notes For Permit 01061036 |
| Permit Number |
01061036 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-08 00:00:00 | *******************DENIED*************** | | | | | | | | | AS PER 1996 NFPA 90A 3-3.4.3 (F), | | | SHAFTS THAT CONSTITUTE AIR DUCTS OR THAT | | | ENCLOSE AIR DUCTS USED FOR THE MOVEMENT | | | OF ENVIRONMENTAL AIR SHALL NOT ENCLOSE | | | PIPING.REFRIGERANT LINES SHALL NOT | | | SHARE THE SAME SHAFT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|