Plan Review Notes
Plan Review Notes For Permit 01061036
Permit Number 01061036
Review Stop M
Sequence Number 2
Notes
Date Text
2001-10-08 00:00:00*******************DENIED***************
  
  
 AS PER 1996 NFPA 90A 3-3.4.3 (F),
 SHAFTS THAT CONSTITUTE AIR DUCTS OR THAT
 ENCLOSE AIR DUCTS USED FOR THE MOVEMENT
 OF ENVIRONMENTAL AIR SHALL NOT ENCLOSE
 PIPING.REFRIGERANT LINES SHALL NOT
 SHARE THE SAME SHAFT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.