| Plan Review Notes For Permit 01061036 |
| Permit Number |
01061036 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-09 00:00:00 | THE EXIT STAIRS ARE REQUIRED TO BE | | | SEPARATED BY AT LEAST 1/2 THE DIAGONAL | | | DISTANCE. THE CODE REFERENCED IN YOUR | | | RESPONSE 5-5.1.4 IN YOUR RESPONSE | | | LETTER DEALS WITH INTERLOCKING STAIRS | | | OR SCISSOR STAIRS. THE 1/3 RULE WILL | | | APPLY IN THE FUTURE WHEN THE NEW FIRE | | | CODE GOES INTO EFFECT NOT NOW. THE | | | DOORS FROM THE TENANT SPACES ON THE | | | SECOND AND THIRD FLOORS ARE NOT | | | SEPARATED THE PROPER DISTANCES APART. | | | THE CONCERN IS THAT WHEN TENANT PLANS | | | ARE SUBMITTED IN THE FUTURE THEY WILL | | | BE ABLE TO BE PERMITTED. NOTES ON THE | | | PLANS INDICATES BATHROOMS WILL BE | | | PROVIDED IN THE FUTURE. PLEASE PROVIDE | | | SOME INDICATION WHERE THEY WILL BE | | | LOCATED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|