Plan Review Notes
Plan Review Notes For Permit 01061036
Permit Number 01061036
Review Stop ENG
Sequence Number 2
Notes
Date Text
2001-10-09 00:00:00FAILED :
 1. ALL THE EXISTING PIPES SHOULD BE
 DIFFERENTIATED FROM NEW ONES.
 2. PLEASE SUBMIT TWO SETS OF CIVIL PLANS
 TO PUBLIC UTILITIES ENGINEERING SERVICES
 FOR ALL THE CONNECTIONS AND LOCATIONS
 OF THE BACKFLOW PREVENTERS, BACKFLOW
 PREVENTERS SHOULD BE LOCATED IN UE.
 3. GROUND SIGN IN UE SHOULD BE RELOCATED
 AND NO NEW SIGNS SHOULD BE PLACED IN UE.
 4. PLEASEVERIFY WITH PUBLIC UTILITIES
 ENGINEERING FOR LOCATION OF EXISTING 8"
 WATER MAIN IN SOUTH EAST CORNER OF THE
 PROPERTY, AS SHOWN, IT IS GOING THROUGH
 THE EXISTING INLET.
 5. PLEASE COORDINATE WITH LANDSCAPING
 ARCHITECT FOR LOCATIONS OF BACKFLOW
 PREVENTERS AND LANDSCAPING AROUND THEM.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI