| 2001-10-02 00:00:00 | BUILDING PLAN REVIEW |
| | ANDERSON - MOORE CONST CORP |
| | PERMIT # 01061036 |
| | 2505 METROCENTRE BLVD |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS 1997 STANDARD BUILDING |
| | CODE |
| | FL ACC CODE= 1997 FLORIDA ACCESSIBILITY |
| | CODE |
| | |
| | COMMENTS : TYPE IV SUPROTECTED / |
| | SPRINKLERED |
| | |
| | 1)- SHEET A1.1HANDICAPPED VAN PARKING |
| | STALL UNDER THE BUILDING: |
| | A)- FL ACC CODE 4.6.3 HANDICAPPED |
| | PARKING SPACES REQUIRE ACCESS |
| | AILES, FOR VAN PARKING THEY MUST |
| | BE 96" AS PER FIG.9(B). |
| | B)- VERTICAL CLEARENCES FOR AN ACCESSI |
| | BLE ROUTE FOR HANDICAPPED VANS |
| | MINIMUM 8'-2"(FL ACC 4.6.5). |
| | C)- 4.6.4 ADDITIONAL SSIGNAGE REQUIRED |
| | "VAN- ACCESSIBLE". |
| | D)- FL ACC CODE 4.6 PARKING & PASSEN- |
| | GER LOADING ZONES, (2) LOCATION:IN |
| | PARKING FACILITIES WHERE ACCESS- |
| | IBLE PEDESTRIAN CROSS WALKS ARE |
| | REQUIRED, THE SHORTEST SAFE ACCESS |
| | IBLE ROUTE OF TRAVEL TO AN ACCESS- |
| | IBLE PEDESTRAIN ENTRANCE OF THE |
| | PARKING FACILITY. |
| | E)- 4.7.7 DETECTABLE WARNINGS. A CURB |
| | RAMP SHALL HAVE A DETECTABLE WARN- |
| | ING COMPLYING WITH 4.92.2. |
| | F)- 4.7.1. LOCATION CURB RAMPS, |
| | (VAN ACCESSIBILITY) CURB RAMPS ARE |
| | TO COMPLY WITH FIG.11 (A) WITH |
| | FLARED SIDES. |
| | |
| | 2)- SBC 1004.1.4 2ND FL.& 3RD FL. IF |
| | THESE ARE SINGLE TENANTS ON EITHER FLOOR |
| | THE DOORS INTO THE TENANT SPACE DO NOT |
| | MET THE REQUIREMENT OF 1/2 THE DIAGONAL |
| | |
| | 3)- WHEN THE TENANT EGRESS DOORS ARE RE- |
| | DESIGNED TO MEET THE 1/2 THE DIAGONAL, |
| | NOTE THAT THE TENANT EGRESS DOORS AT THE |
| | SOUTH END OF THE ACCES CORRIDOR WILL |
| | NEED TO BE RECESSED TO ALLOW FOR THE |
| | ONE-HALF THE REQUIRED WIDTH DURING THE |
| | OPENING PROCESS.(SBC 1012.1.5). |
| | |
| | 4)- SBC TABLE 600 : |
| | 1ST FLOOR OVER 40% OPENINGS 20'/30' |
| | NORTH /EAST EXPOSURES |
| | 2ND FLOOR OVER 40 % OPENINGS 20'/30' |
| | NORTH /EAST EXPOSURES |
| | 3RD FLOOR OK |
| | |
| | 5)- SHEET A2.1 DETAIL #3 SBC 1517.6.4.3. |
| | OVERFLOW SCUPPERS SHALL BE PLACED IN |
| | WALLS NOT LESS THAN 2" NOR MORE THAN 4" |
| | ABOVE THE ROOF DECK. |
| | |
| | 6)- SBC 1204 RESTROOM LOCATION, REMEMBER |
| | THE 1/2 THE DIAGONAL FOR A SINGLE TENANT |
| | FOR EGRESS DOORS WHEN DESIGNING LOCATION |
| | |
| | 7)- SHEET A6-3 INDICATES PENETRATIONS |
| | THROUGH RATED WALLS MISSING PENETRATIONS |
| | THROUGH RATED HORIZONTAL ASSEMBLIES |
| | (FLOORS, OR FLOOR/CEILING ASSEMBLIES) |
| | SBC 705.6. |
| | |
| | 8)- A6.3 DETAILS 1-6 INDICATE THE BUCK |
| | ATTACHMENT INFO WILL BE ON THE STRUCTUR- |
| | AL PLANS, NO DETAILS ARE FOUND. |
| | |
| | 9)- SHEET S5.5 DETAIL 10, WOOD FRAME |
| | SCREEN WALL @ 42'-0. TYPE IV BUILDING. |
| | EXTERIOR WALLSNON-COMBUSTIBLE. |
| | |
| | 10)- SBC 1606.2.6.2COMPONENTS & CLADDING |
| | PRODUCT APPROVAL REPORTS WILLBE REQUIRED |
| | FOR ALL GLAZED OPENINGS, WINDOWS AND |
| | DOORS. IF THE GLAZED OPENINGS DO NOT |
| | HAVE LARGE MISSLE TESTING STORM SHUTTERS |
| | WILL BE REQUIRED.SEE THE CITIES MISSLE |
| | IMPACT PROTECTION STANDARDS, ITEM # 15 |
| | AS TO RESTRICTIONS. SEE ATTACHMENT. |
| | (2) COPIES OF THE PRODUCT TESTING REPORT |
| | WILL BE REQUIRED, THE CITY RECONIZES |
| | THE SBCCI OR DADE COUNTY. |
| | |
| | 11)- SBC 104.2.2 ADITIONAL INFO REQUIRED |
| | SHEET A6-3 DETAIL 3 SUN SCREEN, THE |
| | ATTACHMENT TO THE WALL? WHAT TYPE OF |
| | FASTENERS ARE TO BE USED? THE BOTTOM |
| | FASTENER IS JUST LOCATED INSIDE THE |
| | BOTTOM OF THE LINTEL. |
| | |
| | 12)- SBC 1503.3.2. THE ROOFING ASSEMBLY |
| | IS REQUIRED TO MEET THE WIND ZONES,SHOW |
| | PRODUCT APPROVAL (2) COPIES. |
| | |
| | BUILDING PLAN REVIEW |