2001-10-02 00:00:00BUILDING PLAN REVIEW
 ANDERSON - MOORE CONST CORP
 PERMIT # 01061036
 2505 METROCENTRE BLVD
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS 1997 STANDARD BUILDING
 CODE
 FL ACC CODE= 1997 FLORIDA ACCESSIBILITY
 CODE
  
 COMMENTS : TYPE IV SUPROTECTED /
 SPRINKLERED
  
 1)- SHEET A1.1HANDICAPPED VAN PARKING
 STALL UNDER THE BUILDING:
 A)- FL ACC CODE 4.6.3 HANDICAPPED
 PARKING SPACES REQUIRE ACCESS
 AILES, FOR VAN PARKING THEY MUST
 BE 96" AS PER FIG.9(B).
 B)- VERTICAL CLEARENCES FOR AN ACCESSI
 BLE ROUTE FOR HANDICAPPED VANS
 MINIMUM 8'-2"(FL ACC 4.6.5).
 C)- 4.6.4 ADDITIONAL SSIGNAGE REQUIRED
 "VAN- ACCESSIBLE".
 D)- FL ACC CODE 4.6 PARKING & PASSEN-
 GER LOADING ZONES, (2) LOCATION:IN
 PARKING FACILITIES WHERE ACCESS-
 IBLE PEDESTRIAN CROSS WALKS ARE
 REQUIRED, THE SHORTEST SAFE ACCESS
 IBLE ROUTE OF TRAVEL TO AN ACCESS-
 IBLE PEDESTRAIN ENTRANCE OF THE
 PARKING FACILITY.
 E)- 4.7.7 DETECTABLE WARNINGS. A CURB
 RAMP SHALL HAVE A DETECTABLE WARN-
 ING COMPLYING WITH 4.92.2.
 F)- 4.7.1. LOCATION CURB RAMPS,
 (VAN ACCESSIBILITY) CURB RAMPS ARE
 TO COMPLY WITH FIG.11 (A) WITH
 FLARED SIDES.
  
 2)- SBC 1004.1.4 2ND FL.& 3RD FL. IF
 THESE ARE SINGLE TENANTS ON EITHER FLOOR
 THE DOORS INTO THE TENANT SPACE DO NOT
 MET THE REQUIREMENT OF 1/2 THE DIAGONAL
  
 3)- WHEN THE TENANT EGRESS DOORS ARE RE-
 DESIGNED TO MEET THE 1/2 THE DIAGONAL,
 NOTE THAT THE TENANT EGRESS DOORS AT THE
 SOUTH END OF THE ACCES CORRIDOR WILL
 NEED TO BE RECESSED TO ALLOW FOR THE
 ONE-HALF THE REQUIRED WIDTH DURING THE
 OPENING PROCESS.(SBC 1012.1.5).
  
 4)- SBC TABLE 600 :
 1ST FLOOR OVER 40% OPENINGS 20'/30'
 NORTH /EAST EXPOSURES
 2ND FLOOR OVER 40 % OPENINGS 20'/30'
 NORTH /EAST EXPOSURES
 3RD FLOOR OK
  
 5)- SHEET A2.1 DETAIL #3 SBC 1517.6.4.3.
 OVERFLOW SCUPPERS SHALL BE PLACED IN
 WALLS NOT LESS THAN 2" NOR MORE THAN 4"
 ABOVE THE ROOF DECK.
  
 6)- SBC 1204 RESTROOM LOCATION, REMEMBER
 THE 1/2 THE DIAGONAL FOR A SINGLE TENANT
 FOR EGRESS DOORS WHEN DESIGNING LOCATION
  
 7)- SHEET A6-3 INDICATES PENETRATIONS
 THROUGH RATED WALLS MISSING PENETRATIONS
 THROUGH RATED HORIZONTAL ASSEMBLIES
 (FLOORS, OR FLOOR/CEILING ASSEMBLIES)
 SBC 705.6.
  
 8)- A6.3 DETAILS 1-6 INDICATE THE BUCK
 ATTACHMENT INFO WILL BE ON THE STRUCTUR-
 AL PLANS, NO DETAILS ARE FOUND.
  
 9)- SHEET S5.5 DETAIL 10, WOOD FRAME
 SCREEN WALL @ 42'-0. TYPE IV BUILDING.
 EXTERIOR WALLSNON-COMBUSTIBLE.
  
 10)- SBC 1606.2.6.2COMPONENTS & CLADDING
 PRODUCT APPROVAL REPORTS WILLBE REQUIRED
 FOR ALL GLAZED OPENINGS, WINDOWS AND
 DOORS. IF THE GLAZED OPENINGS DO NOT
 HAVE LARGE MISSLE TESTING STORM SHUTTERS
 WILL BE REQUIRED.SEE THE CITIES MISSLE
 IMPACT PROTECTION STANDARDS, ITEM # 15
 AS TO RESTRICTIONS. SEE ATTACHMENT.
 (2) COPIES OF THE PRODUCT TESTING REPORT
 WILL BE REQUIRED, THE CITY RECONIZES
 THE SBCCI OR DADE COUNTY.
  
 11)- SBC 104.2.2 ADITIONAL INFO REQUIRED
 SHEET A6-3 DETAIL 3 SUN SCREEN, THE
 ATTACHMENT TO THE WALL? WHAT TYPE OF
 FASTENERS ARE TO BE USED? THE BOTTOM
 FASTENER IS JUST LOCATED INSIDE THE
 BOTTOM OF THE LINTEL.
  
 12)- SBC 1503.3.2. THE ROOFING ASSEMBLY
 IS REQUIRED TO MEET THE WIND ZONES,SHOW
 PRODUCT APPROVAL (2) COPIES.
  
 BUILDING PLAN REVIEW
 JIM WITMER