Plan Review Notes
Plan Review Notes For Permit 01061036
Permit Number 01061036
Review Stop P
Sequence Number 1
Notes
Date Text
2001-07-11 00:00:00DENIED;
  
 1.FIRE LINE TO BUILDING SHOULD HAVE A
 DETECTOR CHECK VALVE ASSEMBLY AS
 SHOWN ON PAGE C-4.
  
 2.DOMESTIC WATER TO BUILDING (3") PIPE
 SHALL HAVE A REDUCED PRESSURE,
 BACKFLOW PREVENTER. DETAIL NOT SHOWN.
  
 3.P1-1 SHOW CAULKULATIONS FOR ROOF AREA
 USING 4.5" RAIN FALL PER SPC FIG.
 1108.4. SHOW ADDITIONAL AREA (PARPAET
 WALLS)
  
 4.OVERFLOW SCUPPERS SHALL BE INSTALLED
 PER SBC 15.17.6.4.3 AND SIZED PER SPC
 SEC. 1109.3.
  
 5.BATHROOM FACILITIES ARE REQUIRED IN
 PUBLIC AREAS SPC SEC.401.2.2 AND
 407.2.2.
  
 6.FUTURE SANITARY, WATER, RELIEF AND PAN
 DRAIN LINES WOULD MAKE TENANT BUILD
 OUTS EASIER.
  
 7.SHOW RIZER DIAGRAMS FOR WATER,
 SANITARY AND STORM DRAINAGE.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369