| Plan Review Notes For Permit 01061036 |
| Permit Number |
01061036 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-11 00:00:00 | DENIED; | | | | | | 1.FIRE LINE TO BUILDING SHOULD HAVE A | | | DETECTOR CHECK VALVE ASSEMBLY AS | | | SHOWN ON PAGE C-4. | | | | | | 2.DOMESTIC WATER TO BUILDING (3") PIPE | | | SHALL HAVE A REDUCED PRESSURE, | | | BACKFLOW PREVENTER. DETAIL NOT SHOWN. | | | | | | 3.P1-1 SHOW CAULKULATIONS FOR ROOF AREA | | | USING 4.5" RAIN FALL PER SPC FIG. | | | 1108.4. SHOW ADDITIONAL AREA (PARPAET | | | WALLS) | | | | | | 4.OVERFLOW SCUPPERS SHALL BE INSTALLED | | | PER SBC 15.17.6.4.3 AND SIZED PER SPC | | | SEC. 1109.3. | | | | | | 5.BATHROOM FACILITIES ARE REQUIRED IN | | | PUBLIC AREAS SPC SEC.401.2.2 AND | | | 407.2.2. | | | | | | 6.FUTURE SANITARY, WATER, RELIEF AND PAN | | | DRAIN LINES WOULD MAKE TENANT BUILD | | | OUTS EASIER. | | | | | | 7.SHOW RIZER DIAGRAMS FOR WATER, | | | SANITARY AND STORM DRAINAGE. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|