| 2001-07-24 00:00:00 | ********************DENIED************** | | | | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER ASHRAE 62-89. | | | | | | CONDENSER UNIT STAND SHALL COMPLY WITH | | | THE AMENDED 1997 SMC 304.2.5, | | | MECHANICAL UNITS FOR NEWLY CONSTRUCTED | | | BUILDINGS SHALL BE MOUNTED TO A HEIGHT | | | SUFFICIENTLY ABOVE THE ROOF TO ALLOW | | | THE INSTALLATION OF THE ROOF SYSTEM, | | | AND FOR REPAIRS BENEATH THE UNIT.SUCH | | | A MOUNTING HEIGHT SHALL BE A MINIMUM OF | | | 18 INCHES. | | | | | | CONDENSATE DRAINS ARE NOT DESIGNATED ON | | | PLANS.PLEASE PROVIDE DETAIL OF | | | CONDENSATE LINES AS WELL AS LOCATION OF | | | TERMINATION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388 | | | 8388. |
|