2001-07-24 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 CONDENSER UNIT STAND SHALL COMPLY WITH
 THE AMENDED 1997 SMC 304.2.5,
 MECHANICAL UNITS FOR NEWLY CONSTRUCTED
 BUILDINGS SHALL BE MOUNTED TO A HEIGHT
 SUFFICIENTLY ABOVE THE ROOF TO ALLOW
 THE INSTALLATION OF THE ROOF SYSTEM,
 AND FOR REPAIRS BENEATH THE UNIT.SUCH
 A MOUNTING HEIGHT SHALL BE A MINIMUM OF
 18 INCHES.
  
 CONDENSATE DRAINS ARE NOT DESIGNATED ON
 PLANS.PLEASE PROVIDE DETAIL OF
 CONDENSATE LINES AS WELL AS LOCATION OF
 TERMINATION.
  
  