Plan Review Notes
Plan Review Notes For Permit 01061036
Permit Number 01061036
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-06-21 00:00:001) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 1985 EDITION INSTEAD OF
 1997 EDITION.
 2) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS 3343-00.
 3) ALL UNDERGROUND FIRE LINES ARE TO
 BE LISTED FOR FIRE SERVICE AND COMPLY
 WITH NFPA 24. ALL UNDERGOUND FIRE LINES
 ARE TO BE PRESSURE TESTED IN ACCORDANCE
 WITH NFPA 25.
 4) IT APPEARS THAT THE EXIT STAIRS DO
 NOT MEET THE REQUIRED 1/2 DIAGONAL
 DISTANCE REQUIREMENT. PLEASE ADJUST
 LOCATIONS OF EXIT STAIRS TO MEET THESE
 MINIMUM CODE REQUIREMENTS.
 5) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR COMMON
 AREAS WALLS AND CEILINGS.
 6) A TWO HOUR FIRE SEPARATION IS
 REQUIRED BETWEEN PARKING AREAS AND OTHER
 AREAS OF THE STRUCTURE.
 7) PLEASE INDICATE EXITING AREAS FROM
 THE PARKING AREA.
 8) DOORS 105,106,107,108,AND 101B ARE TO
 PROPERLY FIRE RATED SINCE THE WALL THEY
 ARE IN MUST BE AT LEAST TWO HOUR FIRE
 RATED.
 9) PLEASE PROVIDE UL NUMBER FOR WALL W3.
 10) STAIRS ARE TO COMPLY WITH NEW STAIR
 REQUIREMENTS 4,7,11, 44" WIDE OR 36"
 IF OCCUPANT LOADS ARE LESS THAN 50
 PERSONS.
 11) FIRE ALARM DIAGRAM NOTES INDICATE
 END OF LINE DEVICES ON EACH CIRCUIT.
 FIRE ALARM SYSTEM TO BE CLASS A OR
 FULLY ADDRESSABLE.
 12) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910