| 2001-06-21 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED. |
| | SHOULD READ 1985 EDITION INSTEAD OF |
| | 1997 EDITION. |
| | 2) BUILDING ADDRESS REQUIRED PER CITY |
| | CODE REQUIREMENTS 3343-00. |
| | 3) ALL UNDERGROUND FIRE LINES ARE TO |
| | BE LISTED FOR FIRE SERVICE AND COMPLY |
| | WITH NFPA 24. ALL UNDERGOUND FIRE LINES |
| | ARE TO BE PRESSURE TESTED IN ACCORDANCE |
| | WITH NFPA 25. |
| | 4) IT APPEARS THAT THE EXIT STAIRS DO |
| | NOT MEET THE REQUIRED 1/2 DIAGONAL |
| | DISTANCE REQUIREMENT. PLEASE ADJUST |
| | LOCATIONS OF EXIT STAIRS TO MEET THESE |
| | MINIMUM CODE REQUIREMENTS. |
| | 5) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR COMMON |
| | AREAS WALLS AND CEILINGS. |
| | 6) A TWO HOUR FIRE SEPARATION IS |
| | REQUIRED BETWEEN PARKING AREAS AND OTHER |
| | AREAS OF THE STRUCTURE. |
| | 7) PLEASE INDICATE EXITING AREAS FROM |
| | THE PARKING AREA. |
| | 8) DOORS 105,106,107,108,AND 101B ARE TO |
| | PROPERLY FIRE RATED SINCE THE WALL THEY |
| | ARE IN MUST BE AT LEAST TWO HOUR FIRE |
| | RATED. |
| | 9) PLEASE PROVIDE UL NUMBER FOR WALL W3. |
| | 10) STAIRS ARE TO COMPLY WITH NEW STAIR |
| | REQUIREMENTS 4,7,11, 44" WIDE OR 36" |
| | IF OCCUPANT LOADS ARE LESS THAN 50 |
| | PERSONS. |
| | 11) FIRE ALARM DIAGRAM NOTES INDICATE |
| | END OF LINE DEVICES ON EACH CIRCUIT. |
| | FIRE ALARM SYSTEM TO BE CLASS A OR |
| | FULLY ADDRESSABLE. |
| | 12) NO HYDRAULIC CALCULATIONS PROVIDED |
| | WITH FIRE SPRINKLER DRAWINGS. |
| | |