| 2001-07-03 00:00:00 | FAILED: |
| | 1. ANY WORK WITHIN PUBLIC R.O.W WILL |
| | REQUIRES A SEPARATE PERMIT. |
| | A. IF CITY, CITY ENGINEER'S OFFICE 659- |
| | 8040 |
| | B. IF COUNTY, PALM BEACH COUNTY |
| | 2. ANY NEW CONNECTIONS TO CITY'S |
| | SERVICES WILL REQUIRE A SEPARATE PERMIT |
| | THROUGH PUBLIC UTILITIES ENGINEERING |
| | SERVICES DEPARTMENT. 659-8040 |
| | 3. PLEASE SUBMIT CALCULATIONS FOR STORM |
| | WATER FOR OUR REVIEW AND APPROVAL. |
| | 4. SHEET C-1 REFERS TO 4/A1 FOR DUMPSTER |
| | ENCLOSURE, IT SHOULD REFER TO SP-1, |
| | PLEASE VERIFY. |
| | 5. SHEET C-1 SHOWS 105 LF. 15" CAP |
| | CONNECTING THE CONTROL STRUCTURE (CB) TO |
| | EXISTING 8" WM, IT SHOULD BE CONNECTED |
| | TO EXISTING CB, PLEASE VERIFY. |
| | 6. SHEET C-2 SHOWS THAT, EXISTING 6"SAN. |
| | SVC. CONNECTED TO EXISTING 8" WM.THIS |
| | LINE SHOULD BE 6" EXISTING WATER SVC. |
| | SEE SHEET C-1. |
| | 7. A CLEAN-OUT WILL NEED TO BE INSTALLED |
| | IN THE SANITARY SEWER LATERAL ON THE |
| | PROPERTY, AT BACK OF THE SIDEWALK PER |
| | CITY REQUIREMENT. |
| | 8. PLEASE PROVIDE DETAILS FOR |
| | EXFILTRATIONS PIPES. |
| | |
| | IF ANY QUESTIONS PLEASE CONTACT 659-8096 |
| | EXT. 8492 MOHAMMAD R. AMINI |