Plan Review Notes
Plan Review Notes For Permit 01061036
Permit Number 01061036
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-07-03 00:00:00FAILED:
 1. ANY WORK WITHIN PUBLIC R.O.W WILL
 REQUIRES A SEPARATE PERMIT.
 A. IF CITY, CITY ENGINEER'S OFFICE 659-
 8040
 B. IF COUNTY, PALM BEACH COUNTY
 2. ANY NEW CONNECTIONS TO CITY'S
 SERVICES WILL REQUIRE A SEPARATE PERMIT
 THROUGH PUBLIC UTILITIES ENGINEERING
 SERVICES DEPARTMENT. 659-8040
 3. PLEASE SUBMIT CALCULATIONS FOR STORM
 WATER FOR OUR REVIEW AND APPROVAL.
 4. SHEET C-1 REFERS TO 4/A1 FOR DUMPSTER
 ENCLOSURE, IT SHOULD REFER TO SP-1,
 PLEASE VERIFY.
 5. SHEET C-1 SHOWS 105 LF. 15" CAP
 CONNECTING THE CONTROL STRUCTURE (CB) TO
 EXISTING 8" WM, IT SHOULD BE CONNECTED
 TO EXISTING CB, PLEASE VERIFY.
 6. SHEET C-2 SHOWS THAT, EXISTING 6"SAN.
 SVC. CONNECTED TO EXISTING 8" WM.THIS
 LINE SHOULD BE 6" EXISTING WATER SVC.
 SEE SHEET C-1.
 7. A CLEAN-OUT WILL NEED TO BE INSTALLED
 IN THE SANITARY SEWER LATERAL ON THE
 PROPERTY, AT BACK OF THE SIDEWALK PER
 CITY REQUIREMENT.
 8. PLEASE PROVIDE DETAILS FOR
 EXFILTRATIONS PIPES.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI