2001-07-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE PROVIDE CLARIFICATION ON
 #10 AWG FOR SITE LIGHTING AND VOLTAGE
 DROP.
  
 2)NOTE: PLEASE SEE E2-1. PLEASE NOTE
 THAT HDP SHOWS OCP FOR HP1A AT 200A`S
 AND PANEL SCHEDULE FOR HP1A IS SHOWN
 BEING RATED AT 150A`S. ALSO PLEASE
 NOTE WIRE SIZE IS SHOWN FOR 150A`S.
 PLEASE NOTE THAT ON HDP PANEL HP3A IS
 SHOWN AS 225A W/ 150A OCP AND WIRE
 RATED FOR 200A`S. SEEMS THAT OCP
 PROTECT-ION GOT CROSSED? PLEASE MAKE
 CORRECTIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372