| Plan Review Notes For Permit 01061036 |
| Permit Number |
01061036 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE PROVIDE CLARIFICATION ON | | | #10 AWG FOR SITE LIGHTING AND VOLTAGE | | | DROP. | | | | | | 2)NOTE: PLEASE SEE E2-1. PLEASE NOTE | | | THAT HDP SHOWS OCP FOR HP1A AT 200A`S | | | AND PANEL SCHEDULE FOR HP1A IS SHOWN | | | BEING RATED AT 150A`S. ALSO PLEASE | | | NOTE WIRE SIZE IS SHOWN FOR 150A`S. | | | PLEASE NOTE THAT ON HDP PANEL HP3A IS | | | SHOWN AS 225A W/ 150A OCP AND WIRE | | | RATED FOR 200A`S. SEEMS THAT OCP | | | PROTECT-ION GOT CROSSED? PLEASE MAKE | | | CORRECTIONS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|