Plan Review Notes
Plan Review Notes For Permit 01061036
Permit Number 01061036
Review Stop B
Sequence Number 1
Notes
Date Text
2001-07-24 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01061036
 ADDRESS: 2505 W METROCENTRE BLVD
 "PLAN REVIEW"
 ARCH SONG & ASSOC.
 TEL: (561) 655- 2423
 FAX: (561) 655- 1482
 SBC*= STANDARD BUILDING CODE AMENDMENTS
 1)- FLOOD ZONE: A-8 MINIMUM ELE. 16'-6"
 ELEVATION CERTIFICATE REQUIRED BEFORE
 C.O.
  
 2)- SBC 1804* SOIL REPOPRT WIWTH MINIMUM
 BEARING VALUES/ RECOMENDATIONS FOR
 SOILS.
  
 3)- S. S. 471 ENG: REQUIRES THAT (BOUN-
 DRY SURVEY) ENGINEERS WORK THAT WILL BE-
 COME PUBLIC RECORD BE SIGHED ,SEALED &
 DATED.
  
 4)- *******SBC 1004.1.4*************
 WHERE 2 OR MORE EXITS OR EXIT DOORS ARE
 REQUIRED, AT LEAST 2 OF THE EXITS OR
 EXIT ACCESS DOORS SHALLBE PLACED A DIS
 TANCE APART EQUAL TO NOT LESS THAN ONE
 HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING OR
 AREA SERVED MEASURED IN A STRAIGHT LINE
 BETWEEN SUCH EXITS OR EXIT ACCESS DOORS.
  
 5)- THE SHEET A1-1 THE SECOND FLOOR PLAN
 ONLY DEPICTS ONE EXIT INTO 2 STAIRWELLS
 NOT REMOTE FROM ONE ANOTHER.
  
 6)- THE SAME SHEET SHOWS NO SECOND
 REMOTE EXIT.
  
 *******DO TO THE EXTREME CHANGE THAT
 WILL BE REQUIRED IN THE PLANS THE REVIEW
 IS DISCONTINUED, A THOROUGH REVIEW CAN
 NOT BE ACCOMPLISHED AT THIS TIME.*******
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096- X 8412