| Notes |
| Date |
Text |
| 2001-06-21 00:00:00 | *******************DENIED*************** | | | | | | | | | ONLY ONE COPY OF PLAN SUBMITTED, NEED | | | TWO. | | | | | | PLEASE DESIGNATE R/A SIZE ON PLAN. | | | | | | WHERE IS CONDENSATE BEING DISPOSED OF? | | | NOTE:UNITS LARGER THAN 3 TON SHALL | | | DRAIN TO STORM DRAIN OR APPROVED DRY | | | WELL. (1997 SMC 304.8. #1) | | | | | | WHAT MATERIAL IS DUCTWORK?ALSO SIZE OF | | | DUCT AND CFM BEING DISTRIBUTED. | | | | | | PLEASE INDICATE HOW AHU IS BEING | | | SUPPORTED AND MATERIALS USED. | | | | | | NOTE:AS PER 1997 SMC 304.8.6.1, | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION IS REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|