| Plan Review Notes For Permit 01061001 |
| Permit Number |
01061001 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-21 00:00:00 | REVIEW NOTES:FAILED | | | | | | REFERENCE NFPA-58 & SGC-97 | | | | | | 1) CONTAINERS TO BE MIN. OF 10' APART, | | | AND 10' FROM ANY BLDG. OR EXTERIOR | | | SOURCE OF IGNITION. | | | SECTS. 3-2.2.2 (F), AND TABLE 3-2.2.2 (D | | | | | | 2) UNDERGROUND CONTAINERS TO BE SECURELY | | | ANCHORED PER SEC. 3-2.2.7 (H) | | | | | | 3) PROVIDE PROTECTON AGAINST VEHICULAR | | | DAMAGE PER 3.2.4.8 (B) | | | | | | 4) AN ANODE BAG SHALL BE INSTALLED ON | | | EACH CONTAINER PER 3-2.4.8 (F) | | | | | | 5) SUBMIT MANUFACTURE SPEC. SHEET FOR | | | EACH POOL HEATER TO VERIFY COMPLIENCE | | | WITH STANDARDS OF NFPA 58 & SGC-97 | | | SEC 402. | | | | | | 6) SUBMIT MANUFACTURE SPEC. SHEET ON P.E | | | PIPE, AND SUBMIT A COPY OF THE SIZING | | | TABLE FROM SGC-97 PER SGC SEC. 302. | | | | | | 7) SUBMIT A SITE PLAN WITH WALK-WAYS, | | | DRIVE-WAYS, PARKING LOTS, STRUCTURES, | | | PROPERTY LINES, OR ANY STRUCTURES | | | THAT MAY AFFECT THE PLACING OF THE | | | CONTAINERS. THESE PLANS MUST BE SIGNED | | | AND SEALED BY AN ARCHITECH OR AN | | | ENGINEER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|