| 2001-07-11 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01060951 |
| | 700 S ROSEMARY AVE # 106 |
| | CONT: DITOCCO KONSTRUCTION INC |
| | P: (954) 943-7708 |
| | ARCH: EDMOND LE BANC |
| | P: (561) 585-3403 |
| | |
| | SBC= STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| | 1)- SBC* 104.2.2- WE WILL NEED TO KNOW |
| | THE OCCUPANCIES THAT ARE TO OCCUPY THE |
| | SECOND FLOOR, WE UNDERSTAND THAT THE |
| | TENANT SPACE 202-B4.C MAY BE A NIGHTCLUB |
| | AND THE TENANT SPACE 202 B4.BMAY BE SOME |
| | TYPE OF GYM. |
| | |
| | 2)- TENANT SPACE 202 B4.B (4936 SQ FT) |
| | WILL REQUIRE (2) MEANS OF EGRESS, |
| | SBC 1004.2.1. 2 APPROVED INDEPENDANT |
| | EXITS, ACCESSIBLE TOEACH TENANT AREA |
| | SERVING EVERY STORY. THE MAIN STAIRWAY |
| | WOULD HAVE TO COMPLY WITH RATINGS FOR |
| | MINIMUM FIRE RESISTANCE (TABLE 705.1.2) |
| | FOR SHAFT ENCLOSURES. 1 HR FOR BUSINESS |
| | & MERCANTILE. 2HR. SHAFT RATING (NOTE 2) |
| | FOR ASSEMBLY, FIRST & SECOND FLOOR.SBC |
| | 1006.1 ENCLOSED STAIRWAYS.705.2/T705.1.2 |
| | 3)- TENANT SPACE 202 B4.C THIS SPACE IF |
| | OCCUPIED BY AN ASSEMBLY OCCUPANCY WOULD |
| | ALSO REQUIRE A 2 HR TENANT SEPERATION AS |
| | NOTED ON THE PLANS. SBC 1019.1: THE |
| | MINIMUM AGGREATE WIDTH OF MAIN ENTRANCE |
| | DOORWAYS FOR GROUP A ASSEMBLY OCCUPANC- |
| | IES SHALL BE SUFFICIENT TO ACCOMODATE |
| | 50% OF THE OCCUPANT LOAD. EACH LEVEL OF |
| | A, ASSEMBLY OCUPANCY SHALL HAVE ACCESS |
| | TO A MAIN EXIT AND SHALL BE PROVIDED |
| | WITH ADDITIONAL EXITS OF SUFFICIENT |
| | WIDTH TO ACCONIDATE 1/2 OF THE TOTAL |
| | OCCUPANT LOAD SERVED BY THAT LEVEL. |
| | |
| | THIS WOULD REQUIRE THE FRONT STAIRWAY TO |
| | HAVE A 2 HR RATING, 1 1/2 HR RATING ON |
| | OPENINGS WHICH IS MISSING ON THE EXIST- |
| | ING STAIRWELL DOOR. |
| | |
| | THERE SEEMS TO BE A PROBLEM WITH EXITING |
| | FOR THIS TENANT SPACE, UNDER ASSEMBLY |
| | OCCUPANCY. WHEN WE USE 15 SQ FT/ PERSON |
| | THERE IS A GREAT CONCERN IF THE STAIRS |
| | & DOORWAYS WILL HANDLE THE LOADING |
| | PLEASE SUBMITT A LIFE SAFETY PLAN FOR |
| | THE FIRST FLOOR & SECOND FLOOR SHOWING |
| | THE EXITING, THE REAL PROBLEM!!!! IS |
| | WHEN UNDER A NIGHTCLUB OCCUPANCY WE GO |
| | A MORE CONCENTRATED AREAS FOR DANCE |
| | FLOORS TO 7 SQ FT & 3 SQ FT FOR BARS. |
| | THE DESIGN DOESN'T BEGIN TO WORK FOR |
| | A CONSINTRATION AS THIS MAY BE. |
| | |
| | 4)- SBC 1003.3.5 THE LIFE SAFETY PLAN |
| | NEEDS TO SHOW THE CONVERGING EXITS AND |
| | THE TENANT LOADS THROUGH TO THE EXTERIOR |
| | OF THE BUILDING. |
| | |
| | 5)- SBC 104.2.2* ADDITIONAL INFORMATION |
| | SERVICE CORRIDOR 108: VERIFY THAT THERE |
| | IS A ACCESSIBLE RAMP WITH A HEIGTH TRANS |
| | ITION OF 1'-4"? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |