2001-08-11 00:00:00 
 PLUMBING PLAN REVIEW, PROVISO.
  
 SEPERATE PERMIT FOR NATURAL GAS.
  
 (1) SHT 1 SUBMITTAL FOR SAFTEY SHOWER,
 IF REQUIRED BY MFG OF CHEMICALS.
 SPC-94 SEC 409.9.2 SHOW LOCATION, WATER,
 AND DRAIN CONNECTIONS. SEC 104.3
  
 (2A)SHT 1 PLUMBING NOTES, #7 AIR CHAMBER
 SEC 607.8.3, TO BE ACCESSIBLE & RECHARGE
 ABEL, COMPLY WITH PDI-WH201 ASSE 1010.
 WATER HAMMER ARRESTORS, INSTALL PER MFG.
 FOR SIZE AND PLACEMENT.
  
 (2B) NOTE #15 IF DISSAMILAR METALS ARE
 TO BE JOINED,GALVENIZED FITTINGS NOT PER
 MITTED,SEC 611.2,USE DIELECTRIC COUPLING
 OR NIPPLE.
  
 END OF COMMENTSPAUL SCHMITZ