| Plan Review Notes For Permit 01060851 |
| Permit Number |
01060851 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-08-11 00:00:00 | | | | PLUMBING PLAN REVIEW, PROVISO. | | | | | | SEPERATE PERMIT FOR NATURAL GAS. | | | | | | (1) SHT 1 SUBMITTAL FOR SAFTEY SHOWER, | | | IF REQUIRED BY MFG OF CHEMICALS. | | | SPC-94 SEC 409.9.2 SHOW LOCATION, WATER, | | | AND DRAIN CONNECTIONS. SEC 104.3 | | | | | | (2A)SHT 1 PLUMBING NOTES, #7 AIR CHAMBER | | | SEC 607.8.3, TO BE ACCESSIBLE & RECHARGE | | | ABEL, COMPLY WITH PDI-WH201 ASSE 1010. | | | WATER HAMMER ARRESTORS, INSTALL PER MFG. | | | FOR SIZE AND PLACEMENT. | | | | | | (2B) NOTE #15 IF DISSAMILAR METALS ARE | | | TO BE JOINED,GALVENIZED FITTINGS NOT PER | | | MITTED,SEC 611.2,USE DIELECTRIC COUPLING | | | OR NIPPLE. | | | | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|