| Notes |
| Date |
Text |
| 2001-08-09 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE INFORMATION ON EXHAUST | | | TERMINATION FOR THE FUME HOOD. | | | TERMINATION SHALL COMPLY WITH 506.1, A | | | MINIMUM OF 10' FROM ANY ADJACENT | | | BUILDING, PARKING AREA, ADJACENT | | | PROPERTY LINE, WINDOW, DOOR OR AIR | | | INTAKE OPENINING AND SHALL BE LOCATED | | | AT LEAST 10' FROM ADJOINING GRADE LEVEL. | | | | | | | | | PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | PLEASE PROVIDE THE ABOVE INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|