Plan Review Notes
Plan Review Notes For Permit 01060851
Permit Number 01060851
Review Stop M
Sequence Number 2
Notes
Date Text
2001-08-09 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE INFORMATION ON EXHAUST
 TERMINATION FOR THE FUME HOOD.
 TERMINATION SHALL COMPLY WITH 506.1, A
 MINIMUM OF 10' FROM ANY ADJACENT
 BUILDING, PARKING AREA, ADJACENT
 PROPERTY LINE, WINDOW, DOOR OR AIR
 INTAKE OPENINING AND SHALL BE LOCATED
 AT LEAST 10' FROM ADJOINING GRADE LEVEL.
  
  
 PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2.
  
 PLEASE PROVIDE THE ABOVE INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.